17
-
'10 • PAC-SM-137
A
(4)
Outdoor unit fan control
(a) Outdoor unit fan tap and fan motor speed
Unit: min
-1
Model
Mode
F
an motor tap
71
speed
speed
speed
speed
speed
speed
speed
Cooling/Dehumidifying
200
400
600
710
810
850
950
Heating
200
400
600
710
810
850
950
100
speed
speed
speed
speed
speed
speed
speed
Cooling/Dehumidifying
200
350
600
740
820
870
950
Heating
200
350
600
740
820
870
950
125, 140
speed
speed
speed
speed
speed
speed
speed
Cooling/Dehumidifying
200
370
560
640
745
870
910
Heating
200
370
560
640
800
870
910
(b) Fan tap control during cooling/heating operation
F
an taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the higher.
zone
zone
zone
zone
zone
Tap 5(6)
Tap 5(6)
Tap 5(6)
Tap 4
zone
Tap 5(6)
Tap 5(6)
Tap 4(6)
Tap 3
zone
Tap 4
Tap 4
Tap 3
Tap 2
zone
Tap 3
Tap 3
Tap 2
Tap 1
Note (1) Value in ( ) are for the model 71.
z
one
z
one
Outdoor air temp. (˚C)
15 18
z
one
30 37
z
one
46 48
z
one
Outdoor unit heat exchanger temp. (˚C)
20 30
z
one
33 40
z
one
43 53
z
one
(c) Fan tap control during heating operation
F
an taps are selected depending on the outdoor unit heat exchanger temperature (Tho-R1, R2) and the outdoor air temperature (Tho-A).
Note (1) It is detected by Tho-R1 or R2, whichever the lower.
zone
zone
zone
zone
Tap 3
Tap 3
Tap 4
zone
Tap 3
Tap 4(5)
Tap 5
zone
Tap 4
Tap 5
Tap 6
Note (1) Value in ( ) are for the model 71.
3 9
12 15
-2 0
1 3
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)
z
one
z
one
z
one
z
one
z
one
z
one
(d) Outdoor unit fan control at cooling low outdoor air
1)
When all the following conditions are established after the start of compressor, the following control is implemented.
If the outdoor air temperature (Tho-A) is in the zone
in the cooling/dehumidifying mode, it has elapsed 20
seconds from the start of outdoor unit fan and the outdoor unit fan is at the tap 1 speed, the outdoor unit fan speed is
controlled according to the outdoor unit heat exchanger temperature (Tho-R1, R2).
Note (1) It is detected with Tho-R1 or R2, whichever the higher.
5 10
Retained
Outdoor unit fan speed
-10min
-1
20 30
Outdoor unit fan speed
+10min
-1
z
one
z
one
Outdoor air temp. (˚C)
Outdoor unit heat exchanger temp. (˚C)
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...