(g) Over-current protection current safe controls I, II
Detecting the outdoor unit inverter input (primary) current and the output (secondary) current, if the current values exceed
setting values, the compressor speed (frequency) is controlled to protect the inverter.
Retention
Reduces frequency
at each minute.
Reset
B
A
Current (A)
12
14
16
18
20
22
24
50
40
60
70
80
90
100 110 120 130
Control or reset v
alv
e (A)
Compressor speed (frequency) (rps)
(Fig. C) The control value “A” and the reset value vary depending
on the compressor speed.
Reset valve B
Control valve A
(h) Power transistor temperature protection
1) Protective
control
If the power transistor temperature (detected with TIP) exceeds the setting value, the compressor speed (frequency)
is controlled to suppress the rise of power transistor temperature.
Retention
Reduces compressor frequency
at each minute.
Reset
81
85
Power transistor temp. (°C)
(i)
Anomalous power transistor current
1)
Prevents over-current on the inverter. If the current value in the power transistor exceeds the setting value, the
compressor stops.
2)
If the current value in the power transistor exceeds the specified value and the compressor stops 4 times within 30
minutes,
E
42 is displayed on the remote controller and it enters the anomalous stop mode.
(j)
Anomalous inverter PCB
If the power transistor detects any anomaly for 15 minutes, including the stop of compressor,
E
51 is displayed on the
remote controller and it enters the anomalous stop mode.
(k) Anti-frost control by the compressor frequency control
1)
If the indoor unit heat exchanger temperature (detected with Th
I
-R) exceeds the setting value at 4 minutes after the
start of compressor, the compressor speed (frequency) is controlled to initiate the anti-frost control of indoor unit
heat exchanger.
2)
When there are 3 indoor unit heat exchanger temperatures (Th
I
-R), the lowest temperature is detected.
1.5
3.5
Retention
Reduces compressor frequency
at each minute.
Reset
Indoor unit heat exchanger temp. (°C)
3)
Regarding the anti-frost control by the operation stop, refer to the operation control function by the indoor unit
controller and the cooling, dehumidifying frost prevention of page 10.
Model
Cooling
Heating
Control
value A
Reset
value B
Control
value A
Reset
value B
Primary
current
side
71
15.0
14.0
16.0
15.0
100
13.5 (23.0)
12.5 (22.0)
13.5 (23.0)
12.5 (22.0)
125,
140
11.0 (23.0)
10.0 (22.0)
11.0 (25.0)
10.0 (24.0)
Secandary
current
side
71
13.0
12.0
13.0
12.0
100
11.5 (
F
ig.C) 10.5 (
F
ig.C) 11.5 (
F
ig.C) 10.5 (
F
ig.C)
125,
140
11.5 (
F
ig.C) 10.5 (
F
ig.C) 11.5 (
F
ig.C) 10.5 (
F
ig.C)
Note (1) Value in ( ) are for the single phase models.
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...