Drain pan ON/OFF output control (optional) (Models 1
25
〜
140 only)
1)
Drain pan heater ON conditions
When all of following conditions are met, the drain pan heater is turned ON.
・
Outdoor air temperature (detected with Tho-A) is 3ºC or lower.
・
In the heating mode
・
When the compressor is turned ON
2)
Drain pan heater OFF conditions
When either one of following conditions is met, the drain pan heater is turned OFF.
・
Outdoor air temperature (detected with Tho-A) is 5ºC or higher.
・
When the compressor stop has been detected for 30 minutes continuously
・
In the cooling or dehumidifying mode
Drain pan heater ON
Drain pan heater OFF
Outdoor air temperature (ºC) [Tho-A]
5
3