Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
-
'10 • PAC-SM-137
None
Operates but does not heat
Keeps flashing Stays OFF
Keeps flashing Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
temperature differnce
between return and supply air
10-30degC at
heating?
Check the indoor unit fan operation.
Check the temperature differnce
between return and supply air.
Does the
heat load increase after
installtion?
“ ”
message is displayed (for 3 seconds) when
performing cooling, defrosting and heating
operations from the remote
controller.
Is the
compressor rotation
speed low?
Are the
temperature conditions
of room and outdoor air close
to the rated
conditions?
Mistake in model selection.
Calculate heat load once again.
The unit is operating normally but is
operating under the contol for protecting
compressor or other respective parts.
Check which control “Determination control of
conpressor rotation speed” or “Protective control
by controlling compressor rotation speed” is
appropriate to this phenomenon.
NO
YES
YES
NO
YES
YES
YES
NO
NO
Is the compressor
operating?
NO
YES
NO
Note (1) Outdoor: 7°C, Indoor: 20°C
(1)
WAIT
It is normal.
(This unit is designed to
start in the soft start mode
by detecting the under
dome temperature of
compressor when it restart
after power reset.
It is necessary to replace to
higher capacity one or to
install additional unit.
Compressor refrigerant oil
protection control at starting
is activated. For the contents
of control, refer to the
compressor start control of
the microcomputer control
functions.
Compressor may be
stopped by the error
detection control.
For the contents of control,
refer to anomalous stop
control by controlling
compressor rotation speed
of microcomputor control
functions.
Inspect the followings.
• Minor clogging of filter
• Minor clogging of heat
exchanger
• Minor short-circuit
• Minor shortage of
refrigerant amount
• Poor compression of
compressor
Considering appropriate
operation control, check
suspicious points.
Inspect the followings for
reference.
• Major clogging of filter
• Major clogging of heat
exchanger
• Major short-circuit
• Major shortage of
refrigerant amount
• Compressor protection ON
• Indoor fan tap
• Valid setting of silent mode
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Faulty 4-way valve operation
• Poor compression of
compressor
• Faulty expansion valve
operation
Note:
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...