None
Power supply system error
(Power supply to indoor control PCB)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
AC220/240V
detected between 1 and
2 on the terminal block
of indoor
unit?
NO
NO
Are fuses OK (2 pcs.)?
YES
YES
YES
Is AC19V or
higher detected between Red-
Red (CNW2) at transformer
secondary side?
YES
YES
NO
Is the
check of resistance between
-
of CNW0
OK?
NO
Is the
checked result
of resistance of FM,
LM, etc
OK?
NO
NO
Note(1) FDT, FDTC Series: F200, F201
Other than FDT, FDTC: Fuse between wires
(1)
(2)
(3)
FDT, FDTC Series
FDEN, FDUM,
FDU Series
Note (2) Remove the
transformer
for
other than FDT
or
FDTC
Series.
(CNW1)
Note (3)
for GND
NO
NO
Is DC5V
detected between
-
of CNW2?
NO
Is
AC380/415V
for 3-phase unit detected
between 1, 2 and 3 on the teminal
block of outdoor unit or is AC220/240V
for 1-phase unit detected between
1 and 2 on the terminal
block of outdoor
unit?
YES
YES
YES
YES
Is JX1 open?
Is JX1 open?
Defective outdoor control
PCB (Noise filter)
Misconnection or breakage
of connecting wires
Defective indoor control or
power PCB
ª
Replace.
Replace FM, LM, etc.
Replace fuse.
Defective indoor power
PCB
ª
Replace.
Open JX1.
Defective indoor control
PCB
ª
Replace.
Replace transformer.
Open JX1.
Defective indoor control
PCB
ª
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty transformer
• Faulty indoor control or
power PCB
• Broken harness
• Faulty outdoor control PCB
(Noise filter)
Note:
Error code
Remote controller:
LED
Green
Red
Indoor Stays OFF Stays OFF
Outdoor Stays OFF 2 times flash
Content
'10 • PAC-SM-137
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...