INSPECT I/U
INSPECT I/U
(Connection of 3 units or more remote controller)
Keeps flashing Stays OFF
Keeps flashing 2 times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Reduce to 2 units or less.
Change remote controller
setting to “Master”. (SW1
on remote controller PCB)
Change address. (SW2 on
indoor control PCB)
Change to master. (SW5-1,
2 on indoor control PCB)
Correct
Correct
Defective outdoor control
PCB
ª
Replace.
Broken connecting wire
ª
Correct.
Defective indoor control or
power PCB
ª
Replace.
2. Error detection method
Indoor unit cannot communicate
for more than 30 minutes after
the power on with remote
controller.
3. Condition of Error displayed
Same as above
4. Presumable cause
• Improper setting
• Surrounding environment
• Defective remote controller
communication circuit
• Faulty indoor control or
power PCB
• Faulty outdoor control PCB
Note:
If any error is detected 30 minutes after displaying “
WAIT
” on the remote controller, the display changes to
“INSPECT I/U”.
NO
NO
NO
NO
NO
Are more than
3 units of remote controller
connected?
Does remote
controller display
“Slave”?
YES
Do more than
one indoor units have the
same address?
Is it set to
a slave indoor unit.
SW5-1, 2?
Is there loose
or wrong connection at the termanal
of wiring between indoor and
outdoor units?
Is the
grounding wire connected
properly?
Is approx.
DC20V detected between
-
on the outdoor unit terminal
block?
Is approx.
DC20V detected between
-
on the indoor unit terminal
block?
YES
YES
YES
NO
NO
NO
YES
YES
YES
YES
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
'10 • PAC-SM-137
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...