WAIT
Communication error at
initial operation (2/3)
Keeps flashing
Keeps flashing
Stays OFF
2 times flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is DC5V detected
if the inverter power supply connector (CNI2)
is disconnected?
YES
Diagnosis for when the outdoor
control PCB LED is turned off
NO
NO
A
Shut down the breaker and back on
again the breaker 3 minutes later.
To check method for inverter PCB before
replacment of blown power supply fuse.
B
YES
Does it reset normally?
NO
YES
Isn’t the outdoor
unit controller power supply fuse
(71:20A, 100~140:30A) blown?
Note (1) 1-phase model only
NO
YES
YES
YES
NO
Is AC220/240V
detected at the noise filter
secondary side?
Isn’t fuse
〔
250V, 2A
〕
on the outdoor control
PCB blown?
NO
YES
Is DC5V
detected on the outdoor control PCB (Between
-
of CNI1)?
NO
YES
Is DC5V detected
if the connector of outdoor unit fan motor
is disconnected?
NO
Is DC255-310V detected at CNA2?
(1)
Normal (Malfunction by
noise)
See next page.
Replace noise filter.
Check connection of diode
stack and electrolytic
capacitor by refering main
electrical circuit diagram
Defective outdoor control
PCB
ª
Replace.
Defective outdoor control
PCB
ª
Replace.
Defective outdoor fan
motor
Defective inverter PCB
ª
Replace.
Defective outdoor control
PCB
ª
Replace.
2. Error detection method
3. Condition of Error displayed
4. Presumable cause
• Faulty noise filter
• Faulty indoor control PCB
• Faulty outdoor control PCB
• Faulty inverter PCB
• Faulty fan motor
Note:
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
'10 • PAC-SM-137
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...