Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
-
'10 • PAC-SM-137
E
14
Communication error
between master and slave indoor units
Keeps flashing 3 times flash
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is it
OK the unit
address setting for master
and slave indoor
units?
NO
YES
Isn’t
the remote
controller wiring between
indoor units
defective?
Is it
restored by resetting the
power supply?
Note (1) Set dip switches SW5-1 and SW5-2 as shown in the following table.
(Factory default setting – “Master”)
Master
Slave-a
Slave-b
Slave-c
SW5-1
OFF
OFF
ON
SW5-2
OFF
ON
OFF
ON
ON
Dip
switch
Indoor unit
YES
NO
NO
YES
Correct unit address setting.
Correct wiring.
Defective indoor control
PCB
Replace.
• Malfunction by noise
• Check surrounding
environment.
2.
E
rror detection method
When communication error
between master and slave indoor
units occurs
3. Condition of
E
rror displayed
Same as above
4. Presumable cause
• Unit address setting error
• Broken remote controller wire
• Defective remote controller
wire connection
• Defective indoor control PCB
Note:
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...