83
-
E36
Discharge pipe temperature error
Keeps flashing Stays OFF
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
* For the contents of control, refer to the protective control by controlling
compressor rotation speed and cooling high pressure protective control of
micro computer control function for corresponding models.
Are the
characteristics of
discharge pipe temperature
thermistor
normal?
Is the
discharge pipe temperature
control normal?
NO
YES
Is the
temperature (measured
actually) at detection of
error correct?
YES
YES
Is the
discharge pipe
temperature error persisted
during cooling
operation?
NO
* For the characteristics of discharge
pipe temperature, refer to E39.
YES
NO
NO
Replace discharge pipe
temperature thermistor.
Insufficient refrigerant
amount : Recharge
refrigerant by weighing
proper amount on a scale.
Control operation check *
Defective outdoor control
PCB
ª
Replace.
Check unit side:
• Isn’t filter clogged?
• Are adequate indoor,
outdoor unit installation
spaces?
• Isn’t there any short-
circuit of air?
• Isn’t there any fouling,
clogging on indoor heat
exchanger?
2. Error detection method
For the error detection method,
refer to the protective control by
controlling compressor rotation
speed and cooling high pressure
protective control of micro
computer control function for
corresponding models.
3. Condition of Error displayed
When discharge pipe
temperature anomaly is detected
2 times within 60 minutes or
this anomalous state is detected
60 minutes continuously
including compressor stop.
4. Presumable cause
• Defective outdoor control
PCB
• Defective discharge pipe
temperature thermistor
• Clogged filter
• Indoor, outdoor unit
installation spaces
• Short-circuit of air on indoor,
outdoor units
• Fouling, clogging of heat
exchanger
Note:
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
83
-
'10 • PAC-SM-137
A
73
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...