85
-
E38
Outdoor air temperature
thermistor anomaly
Keeps flashing Stays OFF
Keeps flashing 1 time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is
the outdoor air
temperature thermistor connector
connected properly?
YES
Is the
characteristics of the
outdoor air temperature
thermistor
OK?
NO
For the characteristics of outdoor air
temperature thermistor, see the following graph.
YES
0
5
10
15
20
25
30
35
0
10
20
30
40
50
NO
Temperature-resistance characteristics
Temperature thermistor resistance (k
7
)
Temperature (°C)
(Broken wire)
(Shot circuit)
Correct connector.
Defective outdoor air
temperature thermistor
ª
Replace.
Defective outdoor control
PCB
ª
Replace.
(Defective outdoor air
temperature thermistor
input circuit)
2. Error detection method
Detection of anomalously
low temperature (resistance)
on outdoor air temperature
thermistor
3. Condition of Error displayed
• When the temperature thermistor
detects -45°C or lower for 5
seconds continuously within 2
minutes to 2 minutes 20 seconds
after the compressor ON, the
compressor stops. After 3-minutes
delay, the compressor starts again
automatically, but if this anomalous
temperature is detected 3 times
within 40 minutes.
• When -45°C or lower is detected for
5 seconds continuously within 20
second after compressor ON.
4. Presumable cause
• Defective outdoor control
PCB
• Broken thermistor harness or
temperature sensing section
(Check molding.)
• Disconnected wire connection
(connector)
Note:
Error code
Remote controller:
LED
Green
Red
Indoor
Outdoor
Content
-
85
-
'10 • PAC-SM-137
A
75
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...