'10 • PAC-SM-137
A
Error code
Remote controller:
LED
Green
Red
Outdoor
Content
Keeps flashing 1 time flash
Indoor Keeps flashing Stays OFF
E40
High pressure error (63H1 activated)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Is the
service valve fully
opened?
YES
Has 63H1 activated?
NO
1. During cooling
・
Is the outdoor fan motor
running?
・
Isn’t any short-circuit of air on
the outdoor unit?
・
Are sufficient return air/supply air
space
secured?
2. During heating
・
Isn’t the indoor heat
exchanger temperature thermistor
disconnected from the thermistor
casing?
・
Isn’t the filter clogged?
* Under the condition of
overcharging refirgerant, 63H1
may activate due to delay of
starting the preventive control by
compressor speed control,
because detected heat exhanger
temperature, which conducts
compressor speed control,
becomes lower than normal
condition due to excess
sub-cooling
degree.
On operation
of 63H1
Is 63H1
connector connected
properly?
NO
Is the
electronic expansion
valve connector
connection
OK?
YES
YES
If the power supply breaker is turned OFF and ON too quickly,
E40 may be displayed.
(This is normal.)
NO
YES
If any anomaly
exists on the
electronic
expansion valve
connector
connection, the
power supply must
be reset.
NO
Open service valve.
Correct 63H1 connector.
Correct electronic
expansion valve connector.
Defective outdoor control
PCB
ª
Replace.
(Defective 63H1 input
circuit)
2. Error detection method
When the high pressure switch
63H1 is activated.
Compressor OFF
Compressor ON
3.15 4.15
High pressure (MPa)
3. Condition of Error displayed
If 63H1 turns OFF (opened),
the compressor stops. After
3-minutes delay, the compressor
restarts. If this anomaly occurs
5 times within 60 minutes
or continues for 60 minutes
continuously.
4. Presumable cause
• Short circuit of air flow,
disturbance of air flow and
clogging filter at outdoor heat
exchanger/Breakdown of fan
motor
• Defective outdoor control
PCB
• Defective 63H1 connector
• Defective electronic
expansion valve connector
• Closed service valve
• Mixing of non-condensing gas
(nitrogen, etc.)
Note:
In the protective control range for compressor startup (initial startup after power ON), even if 63H1 is activated only once
(63H1turns OFF), immediately the error is displayed.
77
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...