94
–
'10 • PAC-SM-137
A
The range of temperature setting
When shipped, the range of set temperature differs depending on the operation mode as below.
Heating : 16~30˚C (55~86˚F)
Except heating (cooling, fan, dry, automatic) : 18~30˚C (62~86˚F)
Upper limit and lo
w
er limit of set temperature can be changed
w
ith remote controller.
Upper limit setting: valid during heating operation. Possible to set in the range of 20 to 30˚C (68 to 86˚F).
Lower limit setting: valid except heating (automatic, cooling, fan, dry) Possible to set in the range of 18 to 26˚C (62 to
79˚F).
When you set upper and lower limit by this function, control as below.
1. When TEMP RANGE SET, remote controller function of function setting mode is "INDN CHANGE" (factory setting),
During heating, you cannot set the value exceeding the upper limit.
During operation mode except heating, you cannot set the value below the lower limit.
2. When TEMP RANGE SET, remote controller function of function setting mode is "NO INDN CHANGE"
During heating, even if the value exceeding the upper limit is set, upper limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
During except heating, even if the value lower than the lower limit is set, lower limit value will be sent to the indoor unit.
But, the indication is the same as the temperature set.
Ho
w
to set upper and lo
w
er limit value
1. Stop the air-conditioner, and press (SET) and (MODE) button at the same time for over three
seconds .
The indication changes to "FUNCTION SET ".
2. Press button once, and change to the "TEMP RANGE " indication.
3. Press (SET) button, and enter the temperature range setting mode.
4. Select "UPPER LIMIT " or "LOWER LIMIT " by using button.
5. Press (SET) button to fix.
6. When "UPPER LIMIT " is selected (valid during heating)
Press (SET) button to fix. Indication example: "UPPER 26˚C" (Displayed for two seconds)
After the fixed upper limit value displayed for two seconds, the indication will return to "UPPER LIMIT ".
7. When "LOWER LIMIT " is selected (valid during cooling, dry, fan, automatic)
Indication: " SET UP" "LOWER 18˚C "
8. Press ON/OFF button to finish.
Previous button
If upper limit value is set
If upper limit value is set
If lower limit value is set
If lower limit value is set
Indication: " SET UP" "UPPER 30˚C "
Select the upper limit value with temperature setting button . Indication example: "UPPER 26˚C "
(blinking)
Select the lower limit value with temperature setting button . Indication example: "LOWER 24˚C "
(blinking)
Press (SET) button to fix. Indication for example: "LOWER 24˚C" (Displayed for two seconds)
After the fixed lower limit value displayed for two seconds, the indication will return to "LOWER LIMIT ".
It is possible to finish by pressing
ON/OFF button on the way, but
unfinished change of setting is
unavailable.
During setting, if you press
(RESET) button, you return to the
previous screen.
Summary of Contents for FDEN125VNXVD
Page 101: ... 101 10 PAC SM 137A ...
Page 106: ... 106 10 PAC SM 137A 2 Models FDC100 140VNX 100 140VSX ...
Page 107: ... 107 10 PAC SM 137A ...
Page 108: ... 108 10 PAC SM 137A ...
Page 109: ... 109 10 PAC SM 137A ...
Page 110: ... 110 10 PAC SM 137A ...
Page 111: ... 111 10 PAC SM 137A ...
Page 112: ... 112 10 PAC SM 137A ...
Page 113: ... 113 10 PAC SM 137A ...
Page 114: ... 114 10 PAC SM 137A 5 4 Electric wiring work installation ...
Page 115: ... 115 10 PAC SM 137A ...
Page 116: ... 116 10 PAC SM 137A ...
Page 117: ... 118 10 PAC SM 137A ...
Page 118: ... 118 10 PAC SM 137A ...