9
-
Item
Model
FDTA501
FDCA501HES
Nominal cooling capacity
(1)
W
12500
Nominal heating capacity
(1)
W
13600
Power source
3 Phase, 380/400/415V 50Hz
Cooling input
kW
4.30
Running current (Cooling)
A
7.7
Power factor (Cooling)
%
81
Heating input
kW
3.77
Running current (Heating)
A
6.8
Power factor (Heating)
%
80
Inrush current (L.R.A)
A
67
Noise level
dB(A)
5
52
Exterior dimensions
mm
Unit 365
×
840
×
840
1300
×
970
×
370
Height
×
Width
×
Depth
Panel 35
×
950
×
950
Net weight
kg
38 (Unit:31 Panel:7)
112
Refrigerant equipment
–
ZP54K3E-TFD
×
1
Compressor type & Q’ty
Motor
kW
–
3.75
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Refrigerant control
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.2 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
1.95 (3MAW POW)
Defrost control
MC controlled de-icer
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Propeller fan
×
2
Motor
W
120
×
1
55
×
2
Starting method
Line starting
Line starting
Air flow
CMM
100
Fresh air intake
Available
–
Air filter, Q’ty
Long life filter
×
1(washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
40 (Crank case heater)
Operation control
Wired remote control switch
Operation switch
(Optional : RC-E1)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Abnormal discharge temperature protection.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Decorative Panel
Operation data
(3)
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1 JIS B8616
FDTA501HES
Model FDTA501HES
Powerful mode Hi:48 Me:45 Lo:43
Mild mode Hi:45 Me:43 Lo:40
Powerful mode Hi:32 Me:29 Lo:26
Mild mode Hi:29 Me:26 Lo:23
56