19
-
Item
Model
FDENA601
FDCA601HES
Nominal cooling capacity
(1)
W
14200
Nominal heating capacity
(1)
W
15900
Power source
3 Phase, 380/400/415V 50Hz
Cooling input
kW
4.69
Running current (Cooling)
A
8.0
Power factor (Cooling)
%
85
Heating input
kW
4.38
Running current (Heating)
A
7.2
Power factor (Heating)
%
88
Inrush current (L.R.A)
A
77
Noise level
dB(A)
Exterior dimensions
mm
250
×
1620
×
690
1300
×
970
×
370
Height
×
Width
×
Depth
Net weight
kg
46
126
Refrigerant equipment
–
ZP57K3E-TFD
×
1
Compressor type & Q’ty
Motor
kW
–
4.5
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Refrigerant control
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.9 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
1.66 (3MAW POE)
Defrost control
MC controlled de-icer
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan
×
4
Propeller fan
×
2
Motor
W
40
×
2
55
×
2
Starting method
Line starting
Line starting
Air flow
CMM
100
Fresh air intake
Unavailable
–
Air filter, Q’ty
Polypropylene net
×
2(washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
40 (Crank case heater)
Operation control
Wireless remote control switch (Optional: RCN-E1)
Operation switch
Wired remote control switch (Optional: RC-E1)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Abnormal discharge temperature protection.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP20)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
–
Model FDENA601HES
Operation data
(3)
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1 JIS B8616
FDENA601HES
57
Powerful mode Hi:48 Me:46 Lo:44
Mild mode Hi:46 Me:44 Lo:43
Powerful mode Hi:31 Me:29 Lo:26
Mild mode Hi:29 Me:26 Lo:23