32
-
Item
Model
FDURA601
FDCA601HES
Nominal cooling capacity
(1)
W
14400
Nominal heating capacity
(1)
W
16000
Power source
3 Phase, 380/400/415V 50Hz
Cooling input
kW
4.79
Running current (Cooling)
A
8.2
Power factor (Cooling)
%
84
Heating input
kW
4.63
Running current (Heating)
A
7.5
Power factor (Heating)
%
89
Inrush current (L.R.A)
A
77
Noise level
dB(A)
Hi:43 Lo:38
Exterior dimensions
mm
350
×
1370
×
650
1300
×
970
×
370
Height
×
Width
×
Depth
Net weight
kg
65
126
Refrigerant equipment
–
ZP57K3E-TFD
×
1
Compressor type & Q’ty
Motor
kW
–
4.5
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Refrigerant control
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
3.9 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
1.66 (3MAW POE)
Defrost control
MC controlled de-icer
Air handling equipment
Fan type & Q’ty
Multiblade centrifugal fan
×
2
Propeller fan
×
2
Motor
W
460
×
1
55
×
2
Starting method
Line starting
Line starting
Air flow (Standard)
CMM
Hi: 42 Lo: 33.5
100
Available static pressure
Pa
Standard: 50, Max 130
–
Fresh air intake
–
–
Air filter, Q’ty
Polypropylene net
×
1(washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
40 (Crank case heater)
Operation control
Wired remote control switch
Operation switch
(Optional: RC-E1)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Inter-
nal thermostat for fan motor.
Frost protection thermostat.
Abnormal discharge temperature protection.
Installation data
mm
Liquid line:
φ
9.52 (3/8
″
) Gas line:
φ
15.88 (5/8
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Suction grille
Operation data
(3)
Model FDURA601HES
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1, JIS B8616
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 400V 50Hz.
Notes (1) The data are measured at the following conditions.
FDURA601HES
57