2
-
Item
Model
FDTA151
FDCVA151HEN
Nominal cooling capacity
(1)
W
Nominal heating capacity
(1)
W
Power source
1 Phase, 220/230/240V 50Hz
Cooling input
kW
2.90/2.96
Running current (Cooling)
A
5.1/5.5
Power factor (Cooling)
%
86/75
Heating input
kW
2.54/2.60
Running current (Heating)
A
4.6/4.8
Power factor (Heating)
%
84/75
Inrush current (L.R.A)
A
45
Noise level
dB(A)
35
52
Exterior dimensions
mm
Unit 270
×
840
×
840
595
×
780 (+67)
×
290
Height
×
Width
×
Depth
Panel 35
×
950
×
950
Net weight
kg
31 (Unit:24 Panel:7)
40
Refrigerant equipment
–
5CS102XFD
×
1
Compressor type & Q’ty
Motor
kW
–
0.7
Starting method
–
Line starting
Heat exchanger
Louver fins & inner grooved tubing
Slitted fins & inner grooved tubing
Refrigerant control
Electronic expansion valve
Refrigerant
R410A
Quantity
kg
–
1.55 [Pre-charged up to the piping length of 30m]
Refrigerant oil
r
–
0.48 (RB68A)
Defrost control
MC controlled de-icer
Air handling equipment
Fan type & Q’ty
Turbo fan
×
1
Propeller fan
×
1
Motor
W
14
×
1
34
×
1
Starting method
Line starting
Line starting
Air flow
CMM
41
Fresh air intake
Available
–
Air filter, Q’ty
Long life filter
×
1(washable)
–
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber mount (for compressor)
Electric heater
W
–
20 (Crank case heater)
Operation control
Wired remote control switch
Operation switch
(Optional : RC-E1)
– (Indoor unit side)
Room temperature control
Thermostat by electronics
–
Safety equipment
Internal thermostat for fan motor.
Internal thermostat for fan motor.
Frost protection thermostat.
Abnormal discharge temperature protection.
Installation data
mm
Liquid line:
φ
6.35 (1/4
″
) Gas line:
φ
12.7 (1/2
″
)
Refrigerant piping size
(in)
Connecting method
Flare piping
Drain hose
(Connectable with VP25)
–
Insulation for piping
Necessary (both Liquid & Gas lines)
Accessories
Mounting kit. Drain hose
Optional parts
Decorative Panel
Operation data
(3)
(2) This packaged air-conditioner is manufactured and tested in conformity with the following standard. ISO-T1 “UNITARY AIR-CONDITIONERS”
(3) The operation data indicate when the air-conditioner is operated at 230V 50Hz.
(4) Values in [ ~ ] show the minimum to maximum range.
Notes (1) The data are measured at the following conditions.
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling
27˚C
19˚C
35˚C
24˚C
Heating
20˚C
–
7˚C
6˚C
ISO-T1 JIS B8616
FDTVA151HEN
2
SELECTION DATA
2.1 Specifications
(1)
Ceiling recessed type (FDT)
Model FDTVA151HEN
4000 [1800~4700]
4500 [2000~5400]
1.22 [0.35~1.55]
5.4 [1.6~6.9]
98
1.32 [0.40~1.74]
5.9 [1.8~7.7]
97
5
48
Powerful mode Hi:36 Me:33 Lo:32
Mild mode Hi:33 Me:32 Lo:31
Powerful mode Hi:18 Me:15 Lo:14
Mild mode Hi:15 Me:14 Lo:13