'17 • KX-T-259
-
71-1
-
E11
Address setting error between
master and slave indoor units
K
eeps flashing
K
eeps flashing
1.Applicable model
5. T
roubleshooting
All models
Diagnosis
Countermeasure
• In cases of RC-E5
Return address No. to
“IU …” using [
▲
] or
[
▲
] button.
• In cases of RC-EX3
Menu
Next
IU settings
Select IU
2.
Error detection method
IU address has been set using
the “Master IU address set”
function of remote control.
3.Condition of error displayed
Same as above
4. Presumable cause
Same as above
Note:
Is “Master IU
address set” function of remote
control used?
E11 occurs
YES
Error code
Remote control:
LED
Green
Red
Indoor
Content
IU
IU
IU
R/C
In case the wiring is bel ow and “Master IU address
set” is used, E11 is appeared.
#
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
E11
Address setting error between
master and slave indoor units
Keeps flashing
Stays OFF
Keeps flashing
Stays OFF
–
91
–