2
–
1. SPECIFICATIONS
Models FDT28KXZE1, 36KXZE1, 45KXZE1, 56KXZE1, 71KXZE1
Models
FDT28KXZE1
FDT36KXZE1
FDT45KXZE1
FDT56KXZE1
FDT71KXZE1
Panel model (Option)
Standard: T
-PSA-5A
W
-E
Draft
prevention:
T-PSAE-5A
W
-E
Standard: T
-PSA-5A
W
-E
Draft
prevention: T
-PSAE-5A
W
-E
Standard: T
-PSA-5A
W
-E
Draft
prevention: T
-PSAE-5A
W
-E
Standard: T
-PSA-5A
W
-E
Draft
prevention:
T-PSAE-5A
W
-E
Standard: T
-PSA-5A
W
-E
Draft
prevention:
T-PSAE-5A
W
-E
Nominal cooling capacity*1
kW
2.8
3.6
4.5
5.6
7.1
Nominal heating capacity*2
3.2
4.0
5.0
6.3
8.0
Power source
220-240V ~ 50Hz / 220V ~ 60Hz
220-240V ~ 50Hz / 220V ~ 60Hz
220-240V ~ 50Hz / 220V ~ 60Hz
220-240V ~ 50Hz / 220V ~ 60Hz
220-240V ~ 50Hz / 220V ~ 60Hz
Power consumption
Cooling
kW
0.02 - 0.02 / 0.02
0.03 - 0.03 / 0.03
0.03 - 0.03 / 0.03
0.04 - 0.04 / 0.04
0.08 - 0.08 / 0.08
Heating
0.02 - 0.02 / 0.02
0.03 - 0.03 / 0.03
0.03 - 0.03 / 0.03
0.04 - 0.04 / 0.04
0.08 - 0.08 / 0.08
Running current
Cooling
A
0.20 - 0.19 / 0.20
0.30 - 0.28 / 0.30
0.30 - 0.28 / 0.30
0.36 - 0.33 / 0.36
0.70 - 0.64 / 0.70
Heating
0.20 - 0.19 / 0.20
0.30 - 0.28 / 0.30
0.30 - 0.28 / 0.30
0.36 - 0.33 / 0.36
0.70 - 0.64 / 0.70
Sound Pressure Level
dB(A)
P-Hi
:
33
Hi
:
31 Me
:
29 Lo
:
27
P-Hi
:
34
Hi
:
31 Me
:
29 Lo
:
27
P-Hi
:
35
Hi
:
33 Me
:
31 Lo
:
27
P-Hi
:
38 Hi
:
33 Me
:
31 Lo
:
27
P-Hi
:
47 Hi
:
35 Me
:
32 Lo
:
28
Sound Power Level
49
49
50
55
62
Exterior dimensions Height x Width x Depth
mm
Unit
:
236 × 840 × 840
Panel
:
35 × 950 × 950
Unit
:
236 × 840 × 840
Panel
:
35 × 950 × 950
Unit
:
236 × 840 × 840
Panel
:
35 × 950 × 950
Unit
:
236 × 840 × 840
Panel
:
35 × 950 × 950
Unit
:
236 × 840 × 840
Panel
:
35 × 950 × 950
Exterior appearance (Munsell color)
Plaster White
( 6.8Y8.9/0.2 ) near equivalent
Plaster White
( 6.8Y8.9/0.2 ) near equivalent
Plaster White
( 6.8Y8.9/0.2 ) near equivalent
Plaster White
( 6.8Y8.9/0.2 ) near equivalent
Plaster White
( 6.8Y8.9/0.2 ) near equivalent
Net weight*3
kg
Unit
:
20
Standard panel
:
5
Unit
:
20
Standard panel
:
5
Unit
:
20
Standard panel
:
5
Unit
:
21.5
Standard panel
:
5
Unit
:
21.5
Standard panel
:
5
Refrigerant equipment Heat exchanger
Louver fin & inner grooved tubing
Louver fin & inner grooved tubing
Louver fin & inner grooved tubing
Louver fin & inner grooved tubing
Louver fin & inner grooved tubing
Refrigerant control
Electronic Expansion V
alve
Electronic Expansion V
alve
Electronic Expansion V
alve
Electronic Expansion V
alve
Electronic Expansion V
alve
Air handling equipment Fan type & Q'ty
Turbo fan × 1
Turbo fan × 1
Turbo fan × 1
Turbo fan × 1
Turbo fan × 1
Motor
W
58
58
58
58
58
Starting method
Direct line start
Direct line start
Direct line start
Direct line start
Direct line start
Air flow (Standard)
m
3
/min
P-Hi
:
15 Hi
:
14 Me
:
12 Lo
:
10
P-Hi
:
16 Hi
:
14 Me
:
12 Lo
:
10
P-Hi
:
17 Hi
:
15 Me
:
13 Lo
:
10
P-Hi
:
20 Hi
:
16 Me
:
13 Lo
:
11
P-Hi
:
28 Hi
:
17 Me
:
14 Lo
:
12
Available static pressure
Pa
0
0
0
0
0
Outside air intake
Possible
Possible
Possible
Possible
Possible
Air filter
, Q'ty
Pocket plastic net × 1
(W
ashable)
Pocket plastic net× 1
(W
ashable)
Pocket plastic net× 1
(W
ashable)
Pocket plastic net× 1
(W
ashable)
Pocket plastic net× 1
(W
ashable)
Shock & vibration absorber
Rubber sleeve(for fan motor)
Rubber sleeve(for fan motor)
Rubber sleeve(for fan motor)
Rubber sleeve(for fan motor)
Rubber sleeve(for fan motor)
Insulation (noise & heat)
Polyurethane form
Polyurethane form
Polyurethane form
Polyurethane form
Polyurethane form
Operation control Remote control switch (option)
Wired : RC-EX3, RC-E5, RCH-E3
Wireless : RCN-T
-5A
W
-E2
Wired : RC-EX3, RC-E5, RCH-E3
Wireless : RCN-T
-5A
W
-E2
Wired : RC-EX3, RC-E5, RCH-E3
Wireless : RCN-T
-5A
W
-E2
Wired : RC-EX3, RC-E5, RCH-E3
Wireless : RCN-T
-5A
W
-E2
Wired : RC-EX3, RC-E5, RCH-E3
Wireless : RCN-T
-5A
W
-E2
Room temperature control
Thermostat by electronics
Thermostat by electronics
Thermostat by electronics
Thermostat by electronics
Thermostat by electronics
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Installation data Refrigerant piping size
Liquid line:
φ
6.35 (1/4")
Gas line:
φ
9.52 (3/8")
Liquid line:
φ
6.35 (1/4")
Gas line:
φ
12.7 (1/2")
Liquid line:
φ
6.35 (1/4")
Gas line:
φ
12.7 (1/2")
Liquid line:
φ
6.35 (1/4")
Gas line:
φ
12.7 (1/2")
Liquid line:
φ
9.52 (3/8")
Gas line:
φ
15.88 (5/8")
Connecting method
Flare piping
Flare piping
Flare piping
Flare piping
Flare piping
Refrigerant
R410A
R410A
R410A
R410A
R410A
Drain pump
Built-in Drain pump
Built-in Drain pump
Built-in Drain pump
Built-in Drain pump
Built-in Drain pump
Drain hose
Connectable with VP25
Connectable with VP25
Connectable with VP25
Connectable with VP25
Connectable with VP25
Insulation for piping
Necessary(both Liquid & Gas line)
Necessary(both Liquid & Gas line)
Necessary(both Liquid & Gas line)
Necessary(both Liquid & Gas line)
Necessary(both Liquid & Gas line)
Accessories
Mounting kit,Drain hose
Mounting kit,Drain hose
Mounting kit,Drain hose
Mounting kit,Drain hose
Mounting kit,Drain hose
Exterior dimensions
PJF000Z417
PJF000Z417
PJF000Z417
PJF000Z417
PJF000Z417
Electrical wiring
PJF000Z421
PJF000Z421
PJF000Z421
PJF000Z421
PJF000Z421
Notes (1)
The data are measured at the following conditions.
(2)
This packaged air-conditioner is manufactured and tested in conformity with the following standard.
ISO-T1 "UNIT
AR
Y
AIR-CONDITIONERS"
(3) Draft prevention panel weight*3 : 6kg (4) Option : Motion sensor kit (LB-T
-5W
-E)
Adapted t
o
Ro
HS
directive
Item
Indoor air temperature
Outdoor air temperature
Standards
Operation
DB
WB
DB
WB
Cooling*1
27
℃
19
℃
35
℃
24
℃
ISO-T1
Heating*2
20
℃
7
℃
6
℃
'17 • KX-T-254
A