(c) If the cooling/heating selection signal is given by the external input, the operation mode is transmitted to the remote
control.
■
Selection of cooling/heating external input function
Notes (1) Regarding the priority order for combinations of CnT and CnTA, refer to Page 62.
External input
selection
Cooling/heating
selection
External input
method
Level
External input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
External input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
Pulse
Operation
OFF
Cooling zone
Cooling zone
Heating zone
Heating zone
OFF
ON
ON
Cooling
Heating
Heating
Cooling
Auto, cooling, dry mode command
↑
from remote control
↑
Heating, auto, heating mode command
from remote control
Heating
Cooling
Heating
Cooling
Heating zone
Cooling zone
OFF
OFF
ON
ON
Cooling
Cooling
Auto
Auto
Cooling
↑
Set “Cooling/
Heating” “Pulse”
↑
Auto, cooling, dry mode command
by remote control
↑
Auto, heating mode
command by remote control
↑
After setting “Cooling/heating selection”, the cooling/heating is
selected by the current operation mode
.
During heating:: Set at the heating zone (cooling prohibition zone).
During cooling, dry, auto and fan mode: Set
at cooling zone (heating prohibition zone).
Heating
Heating
Cooling
(24) Room temperature detection temperature compensation during heating
With the standard
the compressor is turned ON/OFF with the thermostat setting temperature. When the thermostat
is likely to turn OFF earlier because the unit is installed at the ceiling where warm air tends to accumulate, the setting can be
changed with the wired remote control indoor unit function “
”. The compressor and the heater are turned ON/OFF at
one of the setting tempe3, +2 or +1°C in order to improve the feeling of heating. The setting temperature, however, has
the upper limit of 30°C.
Compressor
Compressor
Standard
Operation
Stop
Setting temperature
-1
+1
Room temperature (deg)
Operation
Stop
Setting temperature
+2
+4
Room temperature (deg)
When it is set at +3°C
(25) Return air temperature compensation
This is the function to compensate the deviation between the detection temperature by the return air temperature thermistor and
the measured temperature after installing the unit.
(a) It is adjustable in the unit of 0.5°C with the wired remote control indoor unit function “RETURN AIR TEMP”.
• +1.0°C, +1.5°C, +2.0°C
• -1.0°C, -1.5°C, -2.0°C
(b) Compensated temperature is transmitted to the remote control and the outdoor unit.
Note (1) The detection temperature compensation is effective on the indoor unit thermistor only.
-
131
-
'16 • PAC-T-251
(c) If the cooling/heating selection signal is given by the external input, the operation mode is transmitted to the remote
control.
■
Selection of cooling/heating external input function
Notes (1) Regarding the priority order for combinations of CnT and CnTA, refer to Page 62.
External input
selection
Cooling/heating
selection
External input
method
Level
External input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
External input
(CnT or CnTA)
Cooling/heating
Cooling/heating
(Competitive)
Pulse
Operation
OFF
Cooling zone
Cooling zone
Heating zone
Heating zone
OFF
ON
ON
Cooling
Heating
Heating
Cooling
Auto, cooling, dry mode command
↑
from remote control
↑
Heating, auto, heating mode command
from remote control
Heating
Cooling
Heating
Cooling
Heating zone
Cooling zone
OFF
OFF
ON
ON
Cooling
Cooling
Auto
Auto
Cooling
↑
Set “Cooling/
Heating” “Pulse”
↑
Auto, cooling, dry mode command
by remote control
↑
Auto, heating mode
command by remote control
↑
After setting “Cooling/heating selection”, the cooling/heating is
selected by the current operation mode
.
During heating:: Set at the heating zone (cooling prohibition zone).
During cooling, dry, auto and fan mode: Set
at cooling zone (heating prohibition zone).
Heating
Heating
Cooling
(24) Room temperature detection temperature compensation during heating
With the standard
the compressor is turned ON/OFF with the thermostat setting temperature. When the thermostat
is likely to turn OFF earlier because the unit is installed at the ceiling where warm air tends to accumulate, the setting can be
changed with the wired remote control indoor unit function “
”. The compressor and the heater are turned ON/OFF at
one of the setting tempe3, +2 or +1°C in order to improve the feeling of heating. The setting temperature, however, has
the upper limit of 30°C.
Compressor
Compressor
Standard
Operation
Stop
Setting temperature
-1
+1
Room temperature (deg)
Operation
Stop
Setting temperature
+2
+4
Room temperature (deg)
When it is set at +3°C
(25) Return air temperature compensation
This is the function to compensate the deviation between the detection temperature by the return air temperature thermistor and
the measured temperature after installing the unit.
(a) It is adjustable in the unit of 0.5°C with the wired remote control indoor unit function “RETURN AIR TEMP”.
• +1.0°C, +1.5°C, +2.0°C
• -1.0°C, -1.5°C, -2.0°C
(b) Compensated temperature is transmitted to the remote control and the outdoor unit.
Note (1) The detection temperature compensation is effective on the indoor unit thermistor only.
(23)
Emergency stop input
When the external input is selected to “Emergency strop”, it is possible to stop the outdoor unit operation by the external
input to the indoor unit.
(a)
Function setting
Emergency stop input can be selected by the indoor function of wired remote control.
Connector
Indoor function
RC-EX3
RC-E5
CnT
External input 1 : Emergency stop
Emergency stop : Valid
CnTA
External input 2 : Emergency stop
No function
(b)
Emergency stop control
When the external input is OFF, the indoor and outdoor units stop.
The indoor unit receive the external input stops the operation, and the outdoor unit which the stopped indoor unit are
connected stops with [E-63].