'17 • KX-T-254
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
E12
Address setting error
by mixed setting method
Keeps flashing Keeps flashing
Keeps flashing Stays OFF
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't the
automatic setting and
manual setting mixed in the address
setting method for indoor
units?
YES
NO
Review address setting.
Replace indoor unit PCB.
2. Error detection method
Automatic address setting and
manual address setting are mixed
when setting address of indoor
units.
3. Condition of error displayed
Same as above
4. Presumable cause
Mistake in address setting for
indoor unit.
Note:
Address setting method list (Figures in [ ] are for previous Superlink models)
Models for new Superlink protocol
Models for previous Superlink protocol
Indoor unit address setting Outdoor unit
address setting Indoor unit address setting
Outdoor unit
address setting
Indoor unit No. SW Outdoor unit No. SW Outdoor unit No. SW Indoor unit No. SW Outdoor unit No. SW Outdoor unit No. SW
Manual address setting
(New SL)
000-127
00-31
00-31
00-47
00-47
00-47
(
Previous SL
)
[00-47]
[00-47]
[00-47]
Automatic address setting for
single refrigerant system
(New SL)
000
49
49
49
49
49
(
Previous SL
)
Automatic address setting for
multiple refrigerant systems
(New SL)
000
49
00-31
Not available
(
Previous SL
)
Not available
–
96
–