34
-
'19 • PAC-SM-302
(ii) Outdoor unit
Remote control
Indoor control PCB
Location of trouble
Description of trouble
Repair method
Reference
page
Error code Red LED Red LED
Green
LED
Keeps
flashing
Stays OFF
Keeps
flashing
Installation, operation status • Higher outdoor heat exchanger temperature
Repair
74
Outdoor heat exchanger
temperature sensor
• Defective outdoor heat exchanger temperature sensor
Replacement, repair
of temperature
sensor
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Installation, operation status • Higher discharge temperature
Repair
75
Discharge pipe temperature
sensor
• Defective discharge pipe temperature sensor
Replacement, repair
of temperature
sensor
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Outdoor heat exchanger
temperature sensor
• Defective outdoor heat exchanger temperature sensor, broken wire or poor
connector connection
Replacement, repair
of temperature
sensor
76
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Outdoor air temperature
sensor
• Defective outdoor air temperature sensor, broken wire or poor connector
connection
Replacement, repair
of temperature
sensor
77
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Discharge pipe temperature
sensor
• Defective discharge pipe temperature sensor, broken wire or poor connector
connection
Replacement, repair
of temperature
sensor
78
Outdoor control PCB
*• Defective outdoor control PCB (Defective temperature sensor input
circuit)?
Replacement of
PCB
Stays OFF
Keeps
flashing
Installation, operation status • Service valve (gas side) closing operation
Replacement
79
Stays OFF
Keeps
flashing
Outdoor control PCB,
compressor
• Current cut (Anomalous compressor over-current)
Replacement of
PCB
80•81
Installation, operation status • Service valve closing operation
Repair
Stays OFF
Keeps
flashing
Outdoor control PCB
• Defective active filter
Repair
PCB replacement
82
Stays OFF
Keeps
flashing
Fan motor
• Defective fan motor
Replacement
83
Outdoor control PCB
• Defective outdoor control PCB
Stays OFF
Keeps
flashing
Power transistor error
(outdoor control PCB)
• Power transistor error
Replacement of
PCB
84
Stays OFF
Keeps
flashing
Operation status
• Shortage in refrigerant quantity
Repair
85
Installation status
• Service valve closing operation
Service valve
opening check
Stays OFF
Keeps
flashing
• Overload operation
• Overcharge
• Compressor locking
• Current safe stop
Replacement
86
Stays OFF
Keeps
flashing
Compressor, outdoor control
PCB
• Anomalous compressor startup
Replacement
87
Stays OFF
Keeps
flashing
Compressor
• Anomalous compressor rotor lock
Replacement
88
WAIT
or
INSPECT I/U
Stays OFF
Keep
flashing
Indoor-outdoor
connection wire
• Poor connection, breakage of indoor-outdoor unit connection wire
Repair
—
Note (1) * mark in the description of trouble means that, in ordinary diagnosis, it cannot identify the cause definitely, and, if the trouble is repaired by
replacing the part, it is judged consequently that the replaced part was defective.
(iii) Option control in-use
Indoor unit control PCB
Description of trouble
Repair method
Error code Red LED Red LED Green LED
Keeps
flashing Stays OFF
Keeps
flashing • Communication error (Defective communication circuit on the main unit of SC-SL2NA-E or SC-SL4-AE/BE) ete.
Replacement
Summary of Contents for FDT40ZSXW1VH