53
-
'19 • PAC-SM-302
Error code
Remote control:
LED
Green
Red
Indoor Stays OFF Stays OFF
Content
None
Power source system error
(Power source to indoor unit control PCB)
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
NO
Are fuses OK
(F1,2)
YES
YES
Is the
check of resistance between
➀
-
➂
of CNW0
OK?
NO
Is the
checked result
of resistance of FM,
LM, etc
OK?
NO
NO
(1)
Note (1)
➄
for GND
Is DC5V
detected between
➃
-
➄
of CNW2?
NO
YES
YES
YES
Is JX1 open?
Is
AC220/240V
detected between
ձ
and
ղ
on the terminal block
of indoor
unit?
NO
YES
NO
Is
AC380/415V
for 3-phase unit detected
between
ձ
,
ղ
and
ճ
on the teminal
block of outdoor unit or is AC220/240V
for 1-phase unit detected between
ձ
and
ղ
on the terminal
block of outdoor
unit?
YES
Defective outdoor unit
control PCB (Noise filter).
Misconnection or breakage
of connecting wires.
Defective indoor unit
control PCB
➞
Replace.
Replace FM, LM, etc.
Replace fuse.
Defective indoor unit
control PCB
➞
Replace.
Open JX1.
Defective indoor unit
control PCB
➞
Replace.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Misconnection or breakage of
connecting wires
• Blown fuse
• Faulty transformer
• Faulty indoor unit control
PCB
• Broken harness
• Faulty outdoor unit control
PCB (Noise filter)
Note: