Error code
Remote control:
LED
Green
Red
Indoor
Stays OFF
Keeps flashing
Content
WAIT
Communication error at
initial operation (1/3)
1. Applicable model
5. Troubleshooting
All Models
When the remote control LCD
displays “
WAIT
” 2
minutes after the power on.
Diagnosis
Countermeasure
Replace the
power source fuse.
NO
YES
YES
NO
YES
YES
The remote controller LCD
displays “ ”
2 minutes after the power on.
Turn the breaker off once and then
back on again 3 minutes later.
Is normal condition restored?
YES
YES
NO
NO
NO
NO
YES
NO
Isn’t blown
the power source fuse (20A) on the outdoor
unit control?
Is AC220/240V
detected at the secondary side of
outdoor unit sub PCB?
Are OK the
connection wires between the
outdoor sub and the main
PCB’S?
NO
Isn’t F10 fuse (250V, 10A) blown.
Is the
green LED of indoor unit
flashing?
Is the
red LED of indoor unit flashing
twice?
Are wires
connected properly between
the indoor and the outdoor
units?
Is approx.
DC20V detected between
2/N
-
➂
on the outdoor unit terminal
block?
YES
NO
Is approx.
DC20V detected between
➁
-
➂
on the indoor unit terminal
block?
NO
YES
WAIT
See next page.
Defective outdoor unit
PCB
→
Replace.
Connect properly.
Replace fuse.
Defective indoor unit
control PCB
→
Replace.
Replace indoor unit control
PCB.
Defective remote control
→
Replace.
Broken remote control
wire Y
→
Replace.
Correct connection wires
between indoor and
outdoor units.
Defective outdoor unit
PCB
→
Replace.
Defective connection wire.
(broken wire)
Noise.
Defective indoor unit
control PCB
→
Replace.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Blown fuse
• Faulty outdoor unit PCB
• Connection between PCB’s
• Blown fuse on single phase
model
• Faulty indoor unit control
PCB
• Defective remote control
• Broken remote control wire
Note: If any anomaly is detected during communication, the error code E5 is displayed. (Outdoor unit red LED flashes twice.) Inspection
procedure is same as above. (Excluding matters related to connection) When the power source is reset after the occurrence of E5, the
LED will display “
WAIT
”
if the anomaly continues. If the breaker ON/OFF is repeated in a short period of time (within 1 minute),
“
WAIT
”
may be displayed. In such occasion, turn the breaker off and wait for 3 minutes.