72
-
'19 • PAC-SM-302
E21
Defective panel switch operation
Keeps flashing 1-time flash
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Reset the error and close
the grill.
Insufficient push on the
panel switch at the internal
face of grill
➞
Attach 3 mm thick
rubber sheet at the section
where the panel switch
touches the inside of grill.
Close then the grill.
Disconnected, poorly
connected connectors
➞
Reinsert properly.
・
Defective panel switch
or incorrect panel switch
wiring
➞
Replace panel
switch.
・
Broken wire between panel
switch PCB (CNV)
➞
Correct
or replace wire.
Defective indoor unit
control PCB
➞
Replace
indoor unit control PCB.
2. Error detection method
Panel switch (PS) has detected
Open for more than 1 second.
3. Condition of Error displayed
Same as above
4. Presumable cause
• Defective panel switch
• Disconnection of wiring
• Defective indoor unit control
PCB
Note:
Does
matter improve if panel
switch is turned ON forcibly
after resetting
error?
Is grill opened?
NO
YES
NO
YES
YES
Are connectors at right
inserted properly?
Is there
continuity between
#1 – #4 of CNV on indoor unit control PCB
when panel switch operation
is checked?
NO
NO
YES
<Forced panel switch ON>
Put the switch in the state of
ON by fixing the silicone
section of panel switch with
adhesive tape while it is held
down.
<Connectors on PCBs>
Indoor unit control PCB: CNV
Silicone guide
Push to turn ON.
Panel switch
→
To CNV
Error code
Remote control:
LED
Green
Red
Indoor
Content