84
-
'19 • PAC-SM-302
Error code
Remote control:
LED
Green
Red
Content
Indoor
Stays OFF
Keeps flashing
Error code
Remote controller: E51
LED
Green
Red
Indoor
Content
Power transistor error
(Models SRC50, 60)
Keeps flashing Stays Off
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
2. Error detection method
3. Condition of error displayed
4. Presumable cause
Note:
If the power transistor primary
current exceeds the setting value
for 3 seconds, the compressor
stops.
Power transistor primary current
• Outdoor unit PCB anomaly
• Dust on outdoor unit PCB
• Blown F2 fuse
Check soldered
surfaces on the outdoor unit PCB for
foreign matter like dust,
fouling,etc.
Isn
’t F2 fuse
(250V, 20A)blown?
Remove foreign matter
like dust, fouling, etc.
Replace fuse.
Defective outdoor unit
PCB
➞
Replace.
YES
NO
NO
YES
E51
Power transistor anomaly