'14 • KX-T-222
PJG000Z312
Model FDU1100FKXZE1
Model
FDU1100FKXZE1
Cooling Mode
(kW)
15
͠
WB
20
͠
WB
25
͠
WB
28
͠
WB
30
͠
WB
32
͠
WB
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
TC
SHC
20
͠
DB
3.84
3.84
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
25
͠
DB
3.84
3.84
5.31
3.13
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
30
͠
DB
4.95
4.95
5.30
4.97 10.16 3.73 13.63 2.87
0.00
0.00
0.00
0.00
35
͠
DB
6.85
6.85
6.86
6.86 10.00 5.53 13.42 4.67 15.92 4.04 18.62 3.36
40
͠
DB
8.27
8.27
8.28
8.28
9.90
7.30 13.20 6.42 15.65 5.79 18.30 5.10
20
͠
DB
3.94
3.94
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
25
͠
DB
3.94
3.94
5.42
3.21
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
30
͠
DB
5.07
5.07
5.41
5.10 10.37 3.82 13.90 2.93
0.00
0.00
0.00
0.00
35
͠
DB
7.02
7.02
7.03
7.03 10.20 5.67 13.68 4.78 16.24 4.12 18.99 3.43
40
͠
DB
8.48
8.48
8.49
8.49 10.10 7.48 13.46 6.58 15.97 5.93 18.67 5.21
20
͠
DB
4.15
4.15
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
25
͠
DB
4.15
4.15
5.71
3.38
0.00
0.00
0.00
0.00
0.00
0.00
0.00
0.00
30
͠
DB
5.37
5.37
5.70
5.40 10.93 4.03 14.58 3.07
0.00
0.00
0.00
0.00
35
͠
DB
7.43
7.43
7.44
7.44 10.75 5.97 14.42 5.04 17.03 4.34 19.92 3.60
40
͠
DB
8.97
8.97
8.99
8.99 10.64 7.92 14.12 6.93 16.75 6.25 19.58 5.49
Heating Mode
(kW)
Air flow
(m
3
/min)
Outdoor
air temp.
-10
͠
WB
-5
͠
WB
0
͠
WB
4
͠
WB
8
͠
WB
12
͠
WB
-10
͠
DB
12.90
0.00
0.00
0.00
0.00
0.00
-5
͠
DB
11.70
11.70
0.00
0.00
0.00
0.00
0
͠
DB
10.49
10.49
10.50
0.00
0.00
0.00
4
͠
DB
8.88
8.89
8.89
8.90
0.00
0.00
8
͠
DB
7.31
7.32
7.32
7.32
7.33
0.00
12
͠
DB
5.60
5.60
5.60
5.60
5.60
5.60
16
͠
DB
3.70
3.70
3.70
3.70
3.70
3.70
20
͠
DB
2.56
2.56
2.55
2.55
2.55
2.55
-10
͠
DB
13.57
0.00
0.00
0.00
0.00
0.00
-5
͠
DB
12.31
12.31
0.00
0.00
0.00
0.00
0
͠
DB
11.03
11.04
11.05
0.00
0.00
0.00
4
͠
DB
9.34
9.35
9.35
9.36
0.00
0.00
8
͠
DB
7.69
7.70
7.70
7.71
7.71
0.00
12
͠
DB
5.89
5.89
5.89
5.89
5.89
5.89
16
͠
DB
3.89
3.89
3.89
3.89
3.89
3.89
20
͠
DB
2.67
2.67
2.67
2.67
2.66
2.66
-10
͠
DB
14.19
0.00
0.00
0.00
0.00
0.00
-5
͠
DB
12.87
12.87
0.00
0.00
0.00
0.00
0
͠
DB
11.54
11.54
11.55
0.00
0.00
0.00
4
͠
DB
9.77
9.77
9.78
9.79
0.00
0.00
8
͠
DB
8.04
8.05
8.05
8.06
8.06
0.00
12
͠
DB
6.16
6.16
6.16
6.16
6.16
6.16
16
͠
DB
4.07
4.07
4.07
4.07
4.07
4.07
20
͠
DB
2.77
2.77
2.77
2.77
2.77
2.77
Note(1) These data show average statuses out of those possible to occur in the system control.
(2) Symbols are as follows
TC :Total cooling capacity (kW)
SHC :Sensible heat capacity (kW)
(3)
Air flow
(m
3
/min)
Outdoor
air temp.
At heating operation outdoor temperature -5
㷄
DB
䌾
-10
㷄
DB,a wind of 10
㷄
or lower in
temperature is blown out for 5
䌾
10mintes when starting a outdoor air processing unit after ending
a defrosting operation.
(Depending on controls, there may be ranges where the operation is not conducted continuously.
䋩
18
20.5
23
18
20.5
23