2
-
'14 • KX-DB-222D
1.2 Outdoor air processing unit (FDU-F)
Models FDU650FKXZE1, 1100FKXZE1, 1800FKXZE1, 240
0FKXZE1
Models
FDU650FKXZE1
FDU1100FKXZE1
FDU1800FKXZE1
FDU2400FKXZE1
Nominal cooling capacity
kW
9.0
14.0
22.4
28.0
Nominal heating capacity
6.5
55
10.5
62
16.0
68
21.5
70
Power source
220-240V 50Hz / 220V 60Hz
220-240V 50Hz / 220V 60Hz
220-240V 50Hz / 220V 60Hz
220-240V 50Hz / 220V 60Hz
Power consumption
Cooling
kW
0.24 - 0.25 / 0.24
0.35 - 0.36 / 0.35
1.16 - 1.20 / 1.16
1.16 - 1.20 / 1.16
Heating
0.24 - 0.25 / 0.24
0.35 - 0.36 / 0.35
1.16 - 1.20 / 1.16
1.16 - 1.20 / 1.16
Running current
Cooling
A
1.80 - 1.70 / 1.80
2.30 - 2.20 / 2.30
6.80 - 6.50 / 6.80
6.80 - 6.50 / 6.80
Heating
1.80 - 1.70 / 1.80
2.30 - 2.20 / 2.30
6.80 - 6.50 / 6.80
6.80 - 6.50 / 6.80
Sound pressure level
dB(A)
Sound power level
dB(A)
Hi
:
31
Hi
:
37
Hi
:
42
Hi
:
45
Exterior dimensions
Height x Width x Depth
mm
280 × 950 × 635
280 × 1,370 × 740
379 × 1,600 × 893
379 × 1,600 × 893
Net weight
kg
34
54
89
89
Refrigerant equipment
Heat exchanger
Louver fin & inner grooved tubing
Louver fin & inner grooved tubing
Louver fin & inner grooved tubing
Louver fin & inner grooved tubing
Refrigerant control
Electronic expansion valve
Electronic expansion valve
Electronic expansion valve
Electronic expansion valve
Air handling equipment
Fan type & Q'ty
Centrifugal fan × 2
Centrifugal fan × 3
Centrifugal fan × 3
Centrifugal fan × 3
Motor
W
130
100 + 200
130 + 350
130 + 350
Starting method
Direct line start
Direct line start
Direct line start
Direct line start
Air flow(Standard)
m
3
/min
Hi
:
11
Hi
:
18
Hi
:
30
Hi
:
40
External static pressure
Pa
200 (at 11 m
3
/min)
200 (at 18 m
3
/min)
200 (at 30 m
3
/min)
200 (at 40 m
3
/min)
Outside air intake
Possible
Possible
Possible
Possible
Air filter, Q'ty
Procure locally
Procure locally
Procure locally
Procure locally
Shock & vibration absorber
Rubber sleeve (for fan motor)
Rubber sleeve (for fan motor)
Rubber sleeve (for fan motor)
Rubber sleeve (for fan motor)
Insulation (noise & heat)
Polyurethane form
Polyurethane form
Polyurethane form
Polyurethane form
Operation control
Operation switch
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Remote control switch(Option)
Wired: RC-EX1A, RC-E5,RCH-E3
Room temperature control
Thermostat by electronics
Thermostat by electronics
Thermostat by electronics
Thermostat by electronics
Safety equipment
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Overload protection for fan motor
Frost protection thermostat
Installation data
Refrigerant piping size
Liquid line:
φ
9.52 (3/8")
Gas line:
φ
15.88 (5/8")
Liquid line:
φ
9.52 (3/8")
Gas line:
φ
15.88 (5/8")
Liquid line:
φ
9.52 (3/8")
Gas line:
φ
19.05 (3/4")
Liquid line:
φ
9.52 (3/8")
Gas line:
φ
22.22 (7/8")
Connecting method
Flare piping
Flare piping
Brazing
Brazing
Refrigerant
R410A
R410A
R410A
R410A
Drain pump
Built-in Drain pump
Built-in Drain pump
ー
ー
Drain hose
Connectable with VP25 (Standard)
Connectable with VP25 (Standard)
Connectable with VP25 (Standard)
Connectable with VP25 (Standard)
Insulation for piping
Necessary (both Liquid & Gas line)
Necessary (both Liquid & Gas line)
Necessary (both Liquid & Gas line)
Necessary (both Liquid & Gas line)
Accessories
Drain hose
Drain hose
Drain hose
Drain hose
(1) The data are measured at 33
℃
DB 28
℃
WB (68%RH) during cooling and 0
℃
DB -2.9
℃
WB (50%RH) during heating (no frost).
Adapted to
RoHS
directive
P
JG
00
0Z
29
3
C
Wireless: RCN-KIT3-E
Wireless: RCN-KIT3-E
Wireless: RCN-KIT3-E
Wireless: RCN-KIT3-E
Notes
(2) Temperature range of outdoor air must be 20 - 40
℃
DB (32
℃
WB or less) during cooling and -10
℃
- 24
℃
DB during heating.
(3) Sound level indicates the value in an anechoic chamber. During operation these values are somewhat higher due to ambient c
onditions.
(4) Select the breaker size according to the own national stand
ard.
(5) The factory E.S.P. setting is set within the range of 10 -120Pa. When SW8-4 is turned to “ON”, E.S.P. setting range can be
changed to 10 -200Pa. (For RC-EX1A and RC-E5 only)
'14 • KX-T