-
67
-
'14 • KX-T-222
(16) Anomalous fan motor
(a)
After starting the fan motor, if the fan motor speed is 200min
-1
or less is detected for 30 seconds continuously and 4 times
within 60 minutes, then fan motor stops with the anomalous stop (E16).
(b) If the fan motor fails to reach at -50(FDU: -500)
min
-1
less than the required speed, it stops with the anomalous stop (E20).
(17) High ceiling control
When sufficient air flow rate cannot be obtained from the indoor unit which is installed at a room with high ceiling, the air flow
rate can be increased by changing the fan tap. To change the fan tap, use the indoor unit function “FAN SPEED SET” on the
wired remote control.
-
-
-
-
-
-
-
PHi1 - Hi
PHi1 - Hi
PHi1 - Me
PHi1 - Me
PHi1 - Hi - Me
PHi1 - Hi - Me
STANDARD
HIGH SPEED1
HIGH SPEED2
FAN SPEED SET
Hi - Lo
Hi - Lo
Hi - Lo
Hi - Me Except FDT
Except FDT, FDTW, FDTS
Only FDT
Only FDT, FDTW, FDTS
Only FDT, FDTW, FDTS
Hi - Me
Hi - M
Hi - Me - Lo
Hi - Me - Lo
Hi - Me - Lo
PHi1 - PHi1 - Hi - Me
PHi2 - Hi - Me - Lo
PHi2 - PHi1 - Hi - Me
PHi1 - Hi - Me - Lo
PHi2 - Hi - Me - Lo
Indoor unit airflow setting
Series
Fan tap
Notes (1) Factory default is STANDARD.
(2) At the hot-start and heating thermostat OFF, or other, the indoor unit fan is operated at the low speed tap of each setting.
(3) This function is not able to be set with wireless remote controls or simple remote control (RCH-E3)
(18) Abnormal temperature thermistor (return air/indoor heat exchanger) wire/short-circuit detection
(a) Broken wire detection
When the return air temperature thermistor detects -20°C or lower or the heat exchanger temperature thermistor detect
-40°C or lower for 5 seconds continuously, the compressor stops. After a 3-minute delay, the compressor restarts but,
if it is detected again within 60 minutes after the initial detection for 6 minutes continuously, stops again (the return air
temperature thermistor: E7, the heat exchanger temperature thermistor: E6).
(b) Short-circuit detection
If the heat exchanger temperature thermistor detects 70°C or higher for 5 seconds continuously at 2 minutes and 20
seconds after the compressor ON during cooling operation, the compressor stops (E6).
(19) External input/output control (CnT or CnTA)
Be sure to connect the wired remote control to the indoor unit. Without wired remote control remote operation by CnT is not
possible to perform.
・
CnT
・
CnTA
①
Operation output
(CnT-2: XR1)
②
Heating output
(CnT-3: XR2)
③
Thermostat ON output
(CnT-4: XR3)
④
Error output
(CnT-5: XR4)
⑤
Remote operation input
(CnT-6: Volt-free contact)
XR1
1
2
3
4
5
6
XR3
XR4
CnT
Blue
12V
XR2
Option
XR5
■
Priority order for combinations of CnT and CnTA input.
Note (1) Following operation commands are accepted when the operation prohibition is set with CnTA as indicated with *.
Individual operation command from remote control, test run command from outdoor unit and operation command from option device, CNT input.
Reference: Explanation on the codes and the combinations of codes in the table above
1.
In case of CnT “Number”, the CnT “Number” is adopted and CnTA is invalidated.
2.
In case of CnTA “Number”, the CnTA “Number” is adopted and CnT is invalidated.
3.
In case of CnT “Number”/CnTA “Number”, the CnT “Number” and the CnTA “Number” become independent functions each other.
4.
In case of CnT “Number” + CnTA “Number”, the CnT “Number” and the CnTA “Number” become competing functions each other.
5.
In case of CnT “Number” > CnTA “Number”, the function of CnT “Number” supersedes that of CnTA “Number”.
6.
In case of CnT “Number” < CnTA “Number”, the function of CnTA “Number” supersedes that of CnT “Number”.
(The “Number” above means
①
-
⑦
in the table.)
CnTA
Blue
12V
XR6
1
2
Note (1)
CnTA function can be
changed by RC-EX1A.
CnTA
①
Operation
stop level
②
Operation
stop pulse
③
Operation
permission/prohibition
④
Operation
permission/prohibition pulse
⑤
Cooling/heating
selection level
⑥
Cooling/heating
selection pulse
⑦
Emergency
stop
CnT
①
Operation stop level
CnT
①
CnT
①
CnT
① +
CnTA
②
CnT
①
CnT
① /
CnTA
⑤
CnT
① /
CnTA
⑥
CnT
① <
CnTA
⑦
②
Operation stop pulse
CnT
②
CnT
②
CnT
② +
CnTA
③
CnT
②
CnT
② /
CnTA
⑤
CnT
② /
CnTA
⑥
CnT
② <
CnTA
⑦
③
Operation permission/prohibition level CnT
③ >
CnTA
①
CnT
③ >
CnTA
②
CnT
③ +
CnTA
③
CnT
③
CnT
③ /
CnTA
⑤
CnT
③ /
CnTA
⑥
CnT
③ <
CnTA
⑦
④
Operation permission/prohibition pulse CnT
④
CnT
④
CnT
④ +
CnTA
③※
CnT
④
CnT
④ /
CnTA
⑤
CnT
④ /
CnTA
⑥
CnT
④ <
CnTA
⑦
⑤
Cooling/heating selection level CnT
⑤ /
CnTA
①
CnT
⑤ /
CnTA
②
CnT
⑤ /
CnTA
③※
CnT
⑤ /
CnTA
④
CnT
⑤
CnT
⑤
CnT
⑤ /
CnTA
⑦
⑥
Cooling/heating selection pulse CnT
⑥ /
CnTA
①
CnT
⑥ /
CnTA
②
CnT
⑥ /
CnTA
③
CnT
⑥ /
CnTA
④
CnT
⑥
CnT
⑥
CnT
⑥ /
CnTA
⑦
⑦
Emergency stop
CnT
⑦ >
CnTA
①
CnT
⑦ >
CnTA
②
CnT
⑦ >
CnTA
③
CnT
⑦ >
CnTA
④
CnT
⑦ /
CnTA
⑤
CnT
⑦ /
CnTA
⑥
CnT
⑦ +
CnTA
⑦