81
–
Error code
Remote control:
LED
Green
Red
Indoor
Outdoor
Content
'14 • KX-T-222
None
Power source system error
(Power source to remote control)
Stays OFF Keeps lighting
Stays OFF Keeps lighting
1. Applicable model
5. Troubleshooting
All models
Diagnosis
Countermeasure
Isn't there any
loose connection of remote
control wires?
Isn't remote
control wire broken or
short-circuited?
Is 23V
or higher detected
between Brown-Brown at the
transformer secondary
side?
Is
DC18V
detected between
①
-
②
of
CNW2?
Disconnect the
remote control
wires.
NO
Is DC15V or higher
detected between X-Y
of indoor unit terminal
block?
Model equipped
with transformer
(Tr
㧵
)
Models other
than shown
at left
YES
YES
YES
YES
NO
NO
YES
NO
NO
Correct it.
Replace wires.
Replace remote control.
Indoor power PCB
anomaly
Replace it.
Indoor control PCB
anomaly
Replace it.
Replace transformer.
Indoor control PCB
anomaly
Replace it.
2. Error detection method
3. Condition of error displayed
4. Presumable cause
• Remote control wire
breakage/short-circuit
• Remote control anomaly
• Malfunction by noise
• Indoor power PCB anomaly
• Broken harness
• Indoor control PCB anomaly
Note: