background image

13

 PREPARATION OF HEATING

• 

Heat pump type

Heat pump type heating applies the mechanism that draws the heat from the outside air to warm up the room by means of the 
refrigerant.

• 

Defrost operation

During heating operation, frost will be formed on the outdoor unit if the temperature outside the room drops. If left alone, the heating 
efficiency decreases. In order to deal with this, the operation is automatically switched to defrost operation to remove the frost. During 
the period, the air flow of hydro module unit and outdoor unit is stopped and “heating defrost” is displayed.

• 

Outer air temperature and heating capacity

The heating efficiency of hydro module unit decreases as the outside temperature becomes lower. If the capacity of hydro module unit 
for heating is not sufficient, please use other heating device.

• 

Time required until the room temperature increases

Hydro module unit circulates warm water to warm the entire room, so it takes a while to rise up the room temperature. It is 
recommended to start operation earlier on a very cold day.

 

“In operation for defrosting.” display

When frost forms on the OU, the heating performance will decrease. This will cause the unit to automatically 
switch to defrost operation, and hot water from the IO will stop. 
The message “In operation for defrosting.” will be displayed on the message display. After the defrost operation 
has completed, “In operation for defrosting.” will disappear, and the unit will switch back to its normal heating 
operation. 

NOTICE

An auto restart function, which is disabled at the factory setting, is applicable to the remote control. Consult your dealer.

 

What is auto restart

•  When a power failure occurs or the power supply is turned off, the function allows the system to automatically resume operation with the 

remote control setting made set before the power failure when the power supply recovers. If the system is stopped before power failure 
it remains stopped after the power recover.

•  Note that in the following cases it is needed to set again with the remote control.

  Timer setting is cancelled. But the sleep timer recovers after power failure recovers. When recovering from a power failure, holiday 

setting will override the weekly timer setting. And time setting returns to default. To return to original setting, after time setting, 
execute “holiday cancel”.

CAUTION

Make sure to stop the operation before turning off the power supply when the auto restart function is enabled. (If the power supply is 
turned off while the system is operating, the indoor unit pump will start immediately when the power supply is turned on. In addition, the 
outdoor unit starts operating 3 minutes after the power supply is turned on.)

 

AUTO RESTART

 

<WIRED REMOTE CONTROL>

CASES WHEN “IN OPERATION FOR DEFROSTING” IS DISPLAYED

HEATING OPERATION

Please observe the following points in order to use the hydro module unit in a safe and comfortable manner.
Make sure to request your dealer for installation, and do not attempt to do by yourself.

Is the system installed on a wall which durable enough to hang the hydro module unit?
Avoid the place where operation noise cause problems to your neighbors.

Normally the efficiency of the hydro module unit will become lower after a while, because dirt accumulates inside the system. This occurs 
gradually in around 3 years of use, depending on the condition of use and surrounding environment. It is thus necessary to conduct 
inspection maintenance in addition to regular maintenance. We recommend you to consult the dealer from whom you purchased the 
system and make a contract for periodical inspection. (charged).

 

INSTALLATION, RELOCATION, AND INSPECTION MAINTENANCE

 Warning : Make sure to consult a dealer or specialist if it is required to relocate and reinstall the hydro module unit.

If the hydro module unit is installed incorrectly, water leakage, electric shock and/or fire may occur. Note that an installation 
fee will be charged for relocation and installation.

Caution : Make sure to perform grounding work

Do not connect the ground wire to any gas pipe, water pipe, or wires of lightning conductors and telephones. If the ground 
work is not good, it may lead to electric shock.

Caution : A leakage breaker is necessary depending on the installation environment.

If it is not mounted there, it may lead to electric shock.

Only qualified specialists of electrical and grounding work can do these works according to “electric equipment technical standards”.

 

Is the wiring designated for the hydro module unit?

 

Is the remote control mounted correctly?
•  In the case of exposed wiring, is the wiring fixed with the attached screw?
•  Is the attached remote control clamps used for fixing the remote control cord?
•  Is the remote control mounted at a height where children cannot reach?

 

OPERATION RANGE

Please use the system in the following operation range. If the system is operated outside this range, the protection controls 
may be activated to prevent malfunction.

CAUTION

INSTALLATION LOCATION

RELOCATION

INSPECTION MAINTENANCE

ELECTRICAL WORK

Condition

Operation

Circulating water temperature

(HMU outlet)

Temperature outside the room

Humidity inside the room

Cooling operation

Only HMU connection: 

Approx. 7 to 25°C

Mixed use: Approx. 14 to 19°C

Only HMU connection: 

Approx. 15 to 46°C

Mixed use: Approx. 15 to 46°C

Approximately 80% or less

Long operation under high humidity may 
leads to waterdrop under the HMU.

Heating operation

Only HMU connection: 

Approx. 25 (or 30) to 55°C

Mixed use: Approx. 25 (or 30) to 40°C

Only HMU connection: 

Approx. -20 (or -10) to 32°C

Mixed use: Approx. -20 (or -10) to 20°C

(Note) Operation range may differ depending on models. Please check the catalog.

Menu

Direction

Heating

20:20 (Tue)

F1: High power

F2: Energy-saving

Timer

In operation for defrosting.

Set temp

MCD012A001_01_EN.indd   13

MCD012A001_01_EN.indd   13

2022/8/4   15:36:03

2022/8/4   15:36:03

Summary of Contents for HMU140KXZE1

Page 1: ...a maszynowa 2006 42 WE Dyrektywa niskonapięciowa 2014 35 UE Dyrektywa EMC 2014 30 UE Dyrektywa o urządzeniach ciśnieniowych 2014 68 UE Rozporządzenie RoHS 2011 65 EU Rozporządzenie w sprawie ekoprojektu 2009 125 WE Oznaczenie CE ma zastosowanie do systemów zasilanych prądem o częstotliwości 50 Hz HMU140KXZE1 HMU280KXZE1 USER S MANUAL ENGLISH ANWENDERHANDBUCH DEUTSCH ISTRUZIONI PER L USO ITALIANO M...

Page 2: ...MCD012A001_cover indd 2 MCD012A001_cover indd 2 2022 5 30 8 40 59 2022 5 30 8 40 59 ...

Page 3: ...sed throughout the main text of this manual have the following meaning marks mean danger alarm and caution The specified prohibited item is described in the triangle The left mark means Shock hazard alarm marks mean prohibited items The specified prohibited item is described in the circle or in the vicinage marks mean compulsory action or instruction The specified prohibited item is described in t...

Page 4: ...d user maintenance shall not be made by children without supervision INSTALLATION PRECAUTIONS DANGER Make sure to have the installation done by your dealer or a specialist If you install by yourself and the unit is not properly installed water leakage electric shock fire and injuries caused by the drop of the unit may occur The preventive measures that the density of leaked refrigerant does not ex...

Page 5: ...lightning strike may lead to failure Do not wash the unit with water nor place a vase with water on the unit It may cause electric shock or ignition Before cleaning make sure to stop operation and cut off the power Make sure to use proper size of fuse Using steel wire or copper wire may lead to failure or fire Do not store a flammable spray etc near the unit nor blow directly to the unit It may le...

Page 6: ...erature burn injury Before repairing or checking indoor unit be sure to turn off Indoor unit power supply breaker It can result in electric shock or injury due to rotation of indoor unit fan if you perform check or repair with the Indoor unit power supply breaker turned on Place the panels removed for repairing or checking on the stable spot Otherwise dropping or falling may lead to injury PRECAUT...

Page 7: ... display Displays the current time and the room name Icon display Each icon is displayed when one of following settings is going on When the demand control is effective When setting is made from the sub R C When the central control Option is running When the periodical inspection is necessary When the Permission Prohibition setting is made When the weekly timer is set When the peak cut timer is se...

Page 8: ...me of backlight is counted up the backlight turns off When the screen is tapped the backlight lights and all operation buttons are displayed NOTE Do not shut down the power supply immediately after the stop of operation It should be waited for more than 5 minutes till the residual operation time of drain motor is counted up Otherwise it could cause water leakage or breakdown A message Invalid requ...

Page 9: ...etting Administrator settings ADMINISTRATOR SETTINGS ADMINISTRATOR PASSWORD 1 Tap the Menu button on the TOP screen and select User setting Administrator settings The administrator password input screen is displayed Enter the administrator password 2 When the administrator setting menu is displayed tap a desired item 2 Following items can be selected and the Permission or Prohibition can be set fo...

Page 10: ...nation can t be accepted is displayed for 3 seconds Priority order of the timer settings is as follows Set OFF timer by hour clock weekly OFF timer Sleep timer Set ON timer by hour clock weekly ON timer On the TOP screen the timer is displayed from the earliest one out of OFF time of the sleep timer ON time and OFF time SETTING THE TIME 2 The Clock setting screen is displayed Set the dd mm yy with...

Page 11: ...ed is displayed on the screen This is used as the Set ON timer by hour and clock ADVICE Warming up 4 Set the following operating conditions Warming up ON OFF the Main R C only Operation mode 5 Set temp 6 Warming up setting can be made with the main R C only Set the operation mode before setting the set temperature Set ON timer by hour When the set time elapses the hydro module unit starts 1 Tap th...

Page 12: ...etting is added select a setting line No and tap the Change button 6 Detail setting screen for the timer setting contents is displayed Tap the State button to switch between State Enable and State Disable Tap the Type button to switch between the OFF timer and the ON timer Select a desired time at 5 min intervals with the buttons In case of ON timer when the Next button is tapped operating conditi...

Page 13: ...y lead to the failure of hydro module unit Even if not used in winter hydro module unit and outdoor unit should be energized to prevent freezing If hydro module unit is not used for a long period drain the circulating water and turn off the power FOR COMFORTABLE USE FREEZING PREVENTION 2 During silent mode control Outdoor unit silent mode control ON will be displayed on the message display 3 When ...

Page 14: ...nit CAUTION Do not turn off the power supply until the pump stops The hydro module unit system cannot start operating again immediately after stopping During the first 3 minutes after stopping operation it is not possible to perform cooling or heating operation even if the ON OFF button is pressed to indicate operation This is because a circuit for protecting the compressor is activated the pump i...

Page 15: ...lowing points in order to use the hydro module unit in a safe and comfortable manner Make sure to request your dealer for installation and do not attempt to do by yourself Is the system installed on a wall which durable enough to hang the hydro module unit Avoid the place where operation noise cause problems to your neighbors Normally the efficiency of the hydro module unit will become lower after...

Page 16: ... be impaired Replace it when deteriorated or hardened 10 years Drain system parts Drain pan Check the clogging of foreign matters and the flow of drain water Check of peeling off and floating of paint coating Visual inspection There should be no drainage clogging There should be no abnormal rust generation and hole opening Cleaning of drain pan inclination check Repair coating or replace the drain ...

Page 17: ...atmospheric dirt Piping in the unit Sympathetic vibration contact and corrosion of the piping in the unit Sympathetic vibration and contact of capillary tube Visual inspection Visual inspection There should be no abnormal sympathetic vibration sound or corrosion There should be no abnormal sympathetic vibration or contact wear Replace it or readjust the piping when extremely corroded Replace it or...

Page 18: ... Visual inspection Should be of a specified resistance value There should be no deposited foreign matter There should be no abnormal display Replace it if it is outside the specified resistance value Clean with a brush in case of deposited foreign matter adhesion Replace or correct the part 25 000 Hr Pressure sensor temperature sensor Open short circuit earth appearance check Tester visual inspect...

Page 19: ...FDC KXZE2 Series Category HMU Series UK DECLARATION OF CONFORMITY We MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS LTD 2 3 Marunouchi 3 chome Chiyoda ku Tokyo 100 8332 Japan declare under our sole responsibility that the apparatus referred to in this declaration conforms with the following directives Description of apparatus Split Type Air Conditioner Model name Relevant GB Directives Supply of Mach...

Page 20: ...lesex UB11 1ET United Kingdom Tel 44 333 207 4072 Fax 44 333 207 4089 http www mhiae com MHIAE SERVICES B V Wholly owned subsidiary of MITSUBISHI HEAVY INDUSTRIES AIR CONDITIONING EUROPE LTD Herikerbergweg 238 Luna ArenA 1101 CM Amsterdam Netherlands P O Box 23393 1100 DW Amsterdam Netherlands Tel 31 20 406 4535 http www mhiaeservices com MCD012A001_cover indd 4 MCD012A001_cover indd 4 2022 5 30 8...

Reviews: