16

Part Name

Regular Inspection

Preventive Maintenance*

Remarks

Part Name

Details of Inspection

Inspection Method

Criteria <Standard>

Details of Maintenance

Inspection 

Interval

Maintenance Interval

(Used Hours/Duration)

Elapsed Years

1

2

3

4

5

6

7

8

9

10 11 12 13 14 15

Electric and 
electronic 
parts

Crankcase heater

- Conductivity check
-  Insulation resistance measurement
- Appearance check

Tester
500 V mega
Visual inspection

-  It should be in a conducting state
-  The resistance value should be 1 M

Ω

 or more

-  There should be no abnormality

-  Replace it if it is not in a conducting state
-  Replace it if the resistance value is 1 M

Ω

 or less

Every year

Before 

the air-

conditioning 

season

8 years

Consumable 
components

Anti-freezing heater

- Conductivity check
-  Insulation resistance, appearance check

Tester
500 V mega, visual 
inspection

-  It should be in a conducting state
-  The resistance value should be 1 M

Ω

 or more, 

there should be no abnormality

-  Replace it if it is not in a conducting state
-  Replace it if the resistance value is 1 M

Ω

 or less

20,000 Hr

Electric component box 
(including inverter)

-  Circuit insulation resistance check

-  Terminal part, connector looseness check

500 V mega

Driver, visual inspection

-  The resistance value should be 1 M

Ω

 or more

-  There should be no looseness at the connecting 

part

-  Clean with a brush in case of extreme dust adhesion
-  Replace it if the resistance value is 1 M

Ω

 or less

-  Retighten or re-insert it if there is looseness

25,000 Hr

Electrolytic 
capacitor

-  Capacitor (electrolytic) appearance check

Visual inspection

-  There should be no liquid leakage or deformation

-  Appearance check, replace it if there is liquid 

leakage

Smoothing 
capacitor

-  Measurement of electrical capacitance and 

insulation resistance

- Appearance check

Electrostatic instrument, 
500 V mega Tester

-  Should be of speci

fi

 ed volume or more

-  The resistance value should be 1 M

Ω

 or more

-  Replace parts regularly
-  Replace it if the resistance value is 1 M

Ω

 or less

10 years

Consumable 
components

Terminal 
block

-  Terminal part screw looseness, deposit of dirt

Driver, visual 
inspection

-  It should not be loose
-  There should be no deposited foreign matter

-  Retighten it if it is loose.
-  Clean with a brush in case of deposited foreign 

matter adhesion

25,000 Hr

Electrical 
component
(including 
boards, etc.)

-  HIC board short circuit check
-  Visual check of dirt adhesion to the board, etc.

-  Self-diagnosis mode, appearance check

Tester
Visual inspection
Visual inspection

-  Should be of a speci

fi

 ed resistance value

-  There should be no deposited foreign matter

-  There should be no abnormal display

-  Replace it if it is outside the speci

fi

 ed resistance value

-  Clean with a brush in case of deposited foreign 

matter adhesion

-  Replace or correct the part

25,000 Hr

Pressure sensor, 
temperature sensor

-  Open, short circuit, earth, appearance check

Tester, visual 
inspection

-  Should be of a speci

fi

 ed resistance value

-  There should be no cracking or discoloration

-  Replace it in case of disconnection and short 

circuit

5 years

Switch, etc.
(including 
FFB, ELB)

Electromagnetic 
switch
Overcurrent relay

Auxiliary relay, etc.

-  Operation, appearance check

-  Rough contact surface

Visual inspection

Visual inspection

-  There should be no deformation

-  It should operate as prescribed, there should be 

no deformation

-  There should be no deformation or discoloration

-  Replace it in case of malfunction, deformation, and 

discoloration

25,000 Hr

Switching power source 
transformer

-  Output voltage measurement

Tester

-  Output voltage should be within a speci

fi

 ed value

-  Replace it if there is voltage abnormality

10 years

Cooling fan

-  Insulation resistance, abnormal sound generation

500 V mega, audible 
inspection

-  The resistance value should be 1 M

Ω

 or more, 

there should be no abnormal sound

-  Replace it if the resistance value is 1 M

Ω

 or less

-  Replace it in case of fan lock

20,000 Hr

Fuse

- Appearance check

Visual inspection

- There should be no deformation or discoloration

- Replace it when it is shutdown

10 years

Consumable 
components

Note 1)  Random fault is an unexpected failure which occurs before 

the wear is progressed, within the service life of the parts and 
equipment. It is difficult to establish a technological measure 
against the random fault. At the moment, statistical handling is the 
only measure against the random fault.

Note 2)  The elapsed year marked with * assumes the operating time 

as 10 hours/day and 2500 hours/year in a normal operating 
condition without frequent start/stop. This may vary according to 
the operating condition. Please check the calculation basis of the 
elapsed year when making a maintenance contract.

Note 3) 

 illustrates the estimated timing when the wear-out 

failure starts and how the failure rate increases as the time passes.

Explanation of symbols

:  Conduct the cleaning and adjustment according to the inspection result

:  In case of abnormality after inspection, replace or repair the corresponding part.

:  Conduct the periodic replacement (consumable components)

:   Random failure

 :  Wear-out failure

MCD012A001̲01̲EN.indd   16

MCD012A001̲01̲EN.indd   16

2022/05/20   9:16:58

2022/05/20   9:16:58

Summary of Contents for HMU140KXZE1

Page 1: ...a maszynowa 2006 42 WE Dyrektywa niskonapięciowa 2014 35 UE Dyrektywa EMC 2014 30 UE Dyrektywa o urządzeniach ciśnieniowych 2014 68 UE Rozporządzenie RoHS 2011 65 EU Rozporządzenie w sprawie ekoprojektu 2009 125 WE Oznaczenie CE ma zastosowanie do systemów zasilanych prądem o częstotliwości 50 Hz HMU140KXZE1 HMU280KXZE1 USER S MANUAL ENGLISH ANWENDERHANDBUCH DEUTSCH ISTRUZIONI PER L USO ITALIANO M...

Page 2: ...MCD012A001_cover indd 2 MCD012A001_cover indd 2 2022 5 30 8 40 59 2022 5 30 8 40 59 ...

Page 3: ...sed throughout the main text of this manual have the following meaning marks mean danger alarm and caution The specified prohibited item is described in the triangle The left mark means Shock hazard alarm marks mean prohibited items The specified prohibited item is described in the circle or in the vicinage marks mean compulsory action or instruction The specified prohibited item is described in t...

Page 4: ...d user maintenance shall not be made by children without supervision INSTALLATION PRECAUTIONS DANGER Make sure to have the installation done by your dealer or a specialist If you install by yourself and the unit is not properly installed water leakage electric shock fire and injuries caused by the drop of the unit may occur The preventive measures that the density of leaked refrigerant does not ex...

Page 5: ...lightning strike may lead to failure Do not wash the unit with water nor place a vase with water on the unit It may cause electric shock or ignition Before cleaning make sure to stop operation and cut off the power Make sure to use proper size of fuse Using steel wire or copper wire may lead to failure or fire Do not store a flammable spray etc near the unit nor blow directly to the unit It may le...

Page 6: ...erature burn injury Before repairing or checking indoor unit be sure to turn off Indoor unit power supply breaker It can result in electric shock or injury due to rotation of indoor unit fan if you perform check or repair with the Indoor unit power supply breaker turned on Place the panels removed for repairing or checking on the stable spot Otherwise dropping or falling may lead to injury PRECAUT...

Page 7: ... display Displays the current time and the room name Icon display Each icon is displayed when one of following settings is going on When the demand control is effective When setting is made from the sub R C When the central control Option is running When the periodical inspection is necessary When the Permission Prohibition setting is made When the weekly timer is set When the peak cut timer is se...

Page 8: ...me of backlight is counted up the backlight turns off When the screen is tapped the backlight lights and all operation buttons are displayed NOTE Do not shut down the power supply immediately after the stop of operation It should be waited for more than 5 minutes till the residual operation time of drain motor is counted up Otherwise it could cause water leakage or breakdown A message Invalid requ...

Page 9: ...etting Administrator settings ADMINISTRATOR SETTINGS ADMINISTRATOR PASSWORD 1 Tap the Menu button on the TOP screen and select User setting Administrator settings The administrator password input screen is displayed Enter the administrator password 2 When the administrator setting menu is displayed tap a desired item 2 Following items can be selected and the Permission or Prohibition can be set fo...

Page 10: ...nation can t be accepted is displayed for 3 seconds Priority order of the timer settings is as follows Set OFF timer by hour clock weekly OFF timer Sleep timer Set ON timer by hour clock weekly ON timer On the TOP screen the timer is displayed from the earliest one out of OFF time of the sleep timer ON time and OFF time SETTING THE TIME 2 The Clock setting screen is displayed Set the dd mm yy with...

Page 11: ...ed is displayed on the screen This is used as the Set ON timer by hour and clock ADVICE Warming up 4 Set the following operating conditions Warming up ON OFF the Main R C only Operation mode 5 Set temp 6 Warming up setting can be made with the main R C only Set the operation mode before setting the set temperature Set ON timer by hour When the set time elapses the hydro module unit starts 1 Tap th...

Page 12: ...etting is added select a setting line No and tap the Change button 6 Detail setting screen for the timer setting contents is displayed Tap the State button to switch between State Enable and State Disable Tap the Type button to switch between the OFF timer and the ON timer Select a desired time at 5 min intervals with the buttons In case of ON timer when the Next button is tapped operating conditi...

Page 13: ...y lead to the failure of hydro module unit Even if not used in winter hydro module unit and outdoor unit should be energized to prevent freezing If hydro module unit is not used for a long period drain the circulating water and turn off the power FOR COMFORTABLE USE FREEZING PREVENTION 2 During silent mode control Outdoor unit silent mode control ON will be displayed on the message display 3 When ...

Page 14: ...nit CAUTION Do not turn off the power supply until the pump stops The hydro module unit system cannot start operating again immediately after stopping During the first 3 minutes after stopping operation it is not possible to perform cooling or heating operation even if the ON OFF button is pressed to indicate operation This is because a circuit for protecting the compressor is activated the pump i...

Page 15: ...lowing points in order to use the hydro module unit in a safe and comfortable manner Make sure to request your dealer for installation and do not attempt to do by yourself Is the system installed on a wall which durable enough to hang the hydro module unit Avoid the place where operation noise cause problems to your neighbors Normally the efficiency of the hydro module unit will become lower after...

Page 16: ... be impaired Replace it when deteriorated or hardened 10 years Drain system parts Drain pan Check the clogging of foreign matters and the flow of drain water Check of peeling off and floating of paint coating Visual inspection There should be no drainage clogging There should be no abnormal rust generation and hole opening Cleaning of drain pan inclination check Repair coating or replace the drain ...

Page 17: ...atmospheric dirt Piping in the unit Sympathetic vibration contact and corrosion of the piping in the unit Sympathetic vibration and contact of capillary tube Visual inspection Visual inspection There should be no abnormal sympathetic vibration sound or corrosion There should be no abnormal sympathetic vibration or contact wear Replace it or readjust the piping when extremely corroded Replace it or...

Page 18: ... Visual inspection Should be of a specified resistance value There should be no deposited foreign matter There should be no abnormal display Replace it if it is outside the specified resistance value Clean with a brush in case of deposited foreign matter adhesion Replace or correct the part 25 000 Hr Pressure sensor temperature sensor Open short circuit earth appearance check Tester visual inspect...

Page 19: ...FDC KXZE2 Series Category HMU Series UK DECLARATION OF CONFORMITY We MITSUBISHI HEAVY INDUSTRIES THERMAL SYSTEMS LTD 2 3 Marunouchi 3 chome Chiyoda ku Tokyo 100 8332 Japan declare under our sole responsibility that the apparatus referred to in this declaration conforms with the following directives Description of apparatus Split Type Air Conditioner Model name Relevant GB Directives Supply of Mach...

Page 20: ...lesex UB11 1ET United Kingdom Tel 44 333 207 4072 Fax 44 333 207 4089 http www mhiae com MHIAE SERVICES B V Wholly owned subsidiary of MITSUBISHI HEAVY INDUSTRIES AIR CONDITIONING EUROPE LTD Herikerbergweg 238 Luna ArenA 1101 CM Amsterdam Netherlands P O Box 23393 1100 DW Amsterdam Netherlands Tel 31 20 406 4535 http www mhiaeservices com MCD012A001_cover indd 4 MCD012A001_cover indd 4 2022 5 30 8...

Reviews: