205
-
'10 • KX-SM-148
(5) Measures to be taken after check operation
When any display other than “CHO-End” is displayed after completing the judgment of check operation, the meanings of each display
are shown as follows.
After checking the contents of inspection and repairing nonconforming items, perform check operation again.
Code
display
Data
display
Meaning of display
Contents of Inspection
CHL
---
Refrigerant circuit is choked at certain
place.
Operation valve on outdoor unit may be left closed.
Low pressure sensor may be anomalous.
Check the detected pressure displayed on 7-segment and compare it with the
value measured with gauge manifold.
Refrigerant piping or signal wiring may not be connected properly. *1 (See page
207.) Check with Mente PC, etc.
Indoor heat exchanger temperature thermistor may be anomalous or disconnected.
*2 (See page 207.)
Refrigerant may not be charged correctly.
Indoor unit expansion valve may not be operating properly.
Connector of indoor unit expansion valve coil may not be connected. *3 (See page
207.)
Indoor unit expansion valve coil may be disconnected from main body of expansion
valve. *4 (See page 207.)
Outdoor unit PCB may be defective.
CHU
Anomalous
indoor unit
No.
Refrigerant is not circulated in the
indoor unit of indicated No.
Refrigerant piping or signal cables may not be connected properly between indoor
and outdoor units. *1 (See page 207.) Check with Mente PC, etc.
Indoor heat exchanger temperature thermistor may be anomalous or disconnected.
*2 (See page 207.)
Operation valve on outdoor unit may be left closed.
Check it especially when many indoor units No. are displayed in data display column of CHU.
it may be displayed by influence of liquid flooding due to the trouble on any other
indoor unit. If CHJ is displayed at the same time, check preferentially the indoor
unit displaying CHJ and after repairing, perform check operation again.
Refrigerant may not be charged correctly.
Indoor unit expansion valve may not be operating properly.
Connector of indoor unit expansion valve coil may not be connected. *3 (See page
207.)
Indoor unit expansion valve coil may be disconnected from main body of expansion
valve. *4 (See page 207.)
CHJ
Anomalous
indoor unit
No.
Expansion valve on the indoor unit
of indicated No. does not operate
properly.
Indoor heat exchanger temperature thermistor may be anomalous or disconnected.
*2 (See page 207.)
it may be displayed by influence of liquid flooding due to the trouble on any other
indoor unit.
Contamination may be trapped in expansion valve due to installation or transitional cause.
Indoor unit expansion valve may not be operating properly.
Connector of indoor unit expansion valve coil may not be connected. *3 (See page
207.)
Indoor unit expansion valve coil may be disconnected from main body of expansion
valve. *4 (See page 207.)
Refrigerant may not be charged correctly.
CH1
---
Indoor heat exchanger temperature
anomaly.
Indoor heat exchanger temperature thermistor may be anomalous or disconnected.
*2 (See page 207.)
CH3
---
Unable to do indoor EEV trouble check. Unable to do indoor EEV trouble check because of unstable operation.
Summary of Contents for KX6 series
Page 106: ... 104 10 KX SM 148 Models FDC335KXE6M FDCS335KXE6M PCB003Z185 ...
Page 108: ... 106 10 KX SM 148 2 Ceiling cassette 4 way Compact type FDTC Models All moddels A PJA003Z341 ...
Page 111: ... 109 10 KX SM 148 b Duct type Models All models PJC001Z281 ...
Page 112: ... 110 10 KX SM 148 5 Ceiling cassette 1 way type FDTS Model FDTS45KXE6D B PJC001Z195 ...
Page 113: ... 111 10 KX SM 148 Model FDTS71KXE6D B PJC001Z196 ...
Page 116: ... 114 10 KX SM 148 Models FDUM112KXE6D 140KXE6D C PJR002Z259 ...
Page 120: ... 118 10 KX SM 148 Model FDK71KXE6D PHA001Z030 ...
Page 122: ... 120 10 KX SM 148 Models FDE71KXE6D 112KXE6D 140KXE6D C PFA003Z827 ...
Page 123: ... 121 10 KX SM 148 12 Floor standing 2 way type FDFW Models All models A PGF000Z004 ...
Page 127: ... 125 10 KX SM 148 5 APPLICATION DATA 5 1 Installation of indoor unit PJF012D016 a ...
Page 128: ... 126 10 KX SM 148 PJF012D016 A 1 Ceiling cassette 4way type FDT ...
Page 129: ... 127 10 KX SM 148 ...
Page 130: ... 128 10 KX SM 148 ...
Page 141: ... 139 10 KX SM 148 4 Ceiling cassette 1way compact type FDTQ PJC012D121 ...
Page 142: ... 140 10 KX SM 148 ...
Page 143: ... 141 10 KX SM 148 ...
Page 146: ... 144 10 KX SM 148 2 Parts Models QR PNA 14W ER QR PNB 14W ER PJC012D102 h ...
Page 148: ... 146 10 KX SM 148 ...
Page 149: ... 147 10 KX SM 148 5 Ceiling cassette 1way type FDTS PJC012D016 ...
Page 150: ... 148 10 KX SM 148 ...
Page 151: ... 149 10 KX SM 148 ...
Page 152: ... 150 10 KX SM 148 6 Duct connected High static pressure type FDU PJD012D053 ...
Page 153: ... 151 10 KX SM 148 ...
Page 154: ... 152 10 KX SM 148 ...
Page 158: ... 156 10 KX SM 148 8 Duct connected thin Low static pressure type FDUT PJM012D032 B ...
Page 159: ... 157 10 KX SM 148 ...
Page 160: ... 158 10 KX SM 148 ...
Page 161: ... 159 10 KX SM 148 9 Duct connected Compact and Flexible type FDUH PJC012D207 a ...
Page 163: ... 161 10 KX SM 148 ...
Page 164: ... 162 10 KX SM 148 PHA012D039 10 Wall mounted type FDK ...
Page 165: ... 163 10 KX SM 148 ...
Page 166: ... 164 10 KX SM 148 ...
Page 170: ... 168 10 KX SM 148 PGF012D004 12 Floor standing 2 way type FDFW ...
Page 171: ... 169 10 KX SM 148 ...
Page 173: ... 171 10 KX SM 148 13 Outdoor air processing unit type FDU F PJD012D059 ...
Page 174: ... 172 10 KX SM 148 ...
Page 175: ... 173 10 KX SM 148 ...
Page 184: ... 10 KX SM 148 182 ...
Page 212: ... 210 10 KX SM 148 2 model type DIS model type HEAD ...
Page 213: ... 211 10 KX SM 148 2 2 ...
Page 214: ... 212 10 KX SM 148 2 2 2 2 2 ...