'10 • KX-SM-148
(3) Outdoor fan snow protection control
(a) This control is enabled/disabled by entering data into 7-segment display.
(b) Setting method of outdoor fan control
[Starting conditions]
When following conditions are established for 10 minutes continuously.
(i) Snow protection control setting is valid ([P02]
-
1) and outdoor air temperature < 3°C or external input of outdoor fan
snow protection control ON. ([P07]
-
5 and CnS1 is shorted)
➀
Set the Code No. to “P02”.
➁
“0” or “1” is displayed at the data display area.
“0”: Outdoor fan control disabled (Factory setting)
“1”: Outdoor fan control enabled
➂
Press SW7 (Data write/delete) for 3 seconds continuously.
➃
“0” or “1” blinks every 0.5 second at the data display area.
➄
Press SW8 (one digit) to toggle the display back and forth between “0” and “1” (blinking).
➅
If SW7 is pressed for 3 seconds or longer continuously while “0 “ and “1” is blinking, the blinking stops.
With this operation, the enabled/disabled setting of outdoor fan control is stored in memory of EEPROM, and
henceforth the outdoor fan is controlled according to the contents of memory.
➆
Contents of the outdoor fan control are retained even if the power is turned off and backed on again.
(c) Contents of outdoor fan snow protection control
➀
If the outdoor air temperature drops 3°C or lower when the unit is all stop or error stop, the outdoor fan runs at the
rating speed (7th speed) once every 10 minutes.
➁
The outdoor fan runs for 30 seconds.*
*Operation time outdoor fan is changeable from 10 to 600 seconds by [P03]
➂
During this snow protection control, the compressor’s magnetic contactor (52X1 52X2) is ON.
(d) End conditions of outdoor fan snow protection control
When folowing conditions are established.
(i) Snow protection control setting is invalid ([P02]
-
0) or outdoor air temperature > 5°C and external input of outdoor
fan snow protection control OFF ([P07]-[5] and CnSlis opend).
(ii) Compressor ON
(iii) During all stop by anomaly
Valid
Invalid
Outdoor air temperature (°C )
3
5
<Outdoor air temperature condition at snow protection control>
(4) External output
This function is used in order to operate the external optional devices in conjunction with relay outputs of the respective
operation information from outdoor unit.
[External output function]
External output function of CnZ1 can be switched by changing of [P06] on 7-segment display as mentioned below.
0: Operation output
• When the outdoor unit operation mode is “Operation”, the external output relay is turned ON.
(Note) The “Operation” includes not only compressor ON mode but also Fan mode and thermostat OFF mode under the condition of remote controller
ON. But the anomalous stop is excluded.
1: Error output
• It is turned ON at anomalous stop, and turned OFF when “CHECK” and “RESET” buttons on remote controller are
pressed simutaneously after recovering from the anomaly. Even if “CHECK” and “RESET” buttons are pressed before
recovering from the anomaly, it is not turned OFF, but when recovering from the anomaly later, it is automatically
turned OFF.
2: Compressor ON output
• It is turned ON when the compressor is ON.
3: Fan ON output
• It is turned ON when the outdoor fan speed command > 0.
4: Oil return operation output
• This is turned ON during the oil return operation.
5: High pressure control output to water spraying device, etc.
• This is turned ON when the high pressure > 3.3 MPa during cooling operation.
Summary of Contents for KX6 series
Page 106: ... 104 10 KX SM 148 Models FDC335KXE6M FDCS335KXE6M PCB003Z185 ...
Page 108: ... 106 10 KX SM 148 2 Ceiling cassette 4 way Compact type FDTC Models All moddels A PJA003Z341 ...
Page 111: ... 109 10 KX SM 148 b Duct type Models All models PJC001Z281 ...
Page 112: ... 110 10 KX SM 148 5 Ceiling cassette 1 way type FDTS Model FDTS45KXE6D B PJC001Z195 ...
Page 113: ... 111 10 KX SM 148 Model FDTS71KXE6D B PJC001Z196 ...
Page 116: ... 114 10 KX SM 148 Models FDUM112KXE6D 140KXE6D C PJR002Z259 ...
Page 120: ... 118 10 KX SM 148 Model FDK71KXE6D PHA001Z030 ...
Page 122: ... 120 10 KX SM 148 Models FDE71KXE6D 112KXE6D 140KXE6D C PFA003Z827 ...
Page 123: ... 121 10 KX SM 148 12 Floor standing 2 way type FDFW Models All models A PGF000Z004 ...
Page 127: ... 125 10 KX SM 148 5 APPLICATION DATA 5 1 Installation of indoor unit PJF012D016 a ...
Page 128: ... 126 10 KX SM 148 PJF012D016 A 1 Ceiling cassette 4way type FDT ...
Page 129: ... 127 10 KX SM 148 ...
Page 130: ... 128 10 KX SM 148 ...
Page 141: ... 139 10 KX SM 148 4 Ceiling cassette 1way compact type FDTQ PJC012D121 ...
Page 142: ... 140 10 KX SM 148 ...
Page 143: ... 141 10 KX SM 148 ...
Page 146: ... 144 10 KX SM 148 2 Parts Models QR PNA 14W ER QR PNB 14W ER PJC012D102 h ...
Page 148: ... 146 10 KX SM 148 ...
Page 149: ... 147 10 KX SM 148 5 Ceiling cassette 1way type FDTS PJC012D016 ...
Page 150: ... 148 10 KX SM 148 ...
Page 151: ... 149 10 KX SM 148 ...
Page 152: ... 150 10 KX SM 148 6 Duct connected High static pressure type FDU PJD012D053 ...
Page 153: ... 151 10 KX SM 148 ...
Page 154: ... 152 10 KX SM 148 ...
Page 158: ... 156 10 KX SM 148 8 Duct connected thin Low static pressure type FDUT PJM012D032 B ...
Page 159: ... 157 10 KX SM 148 ...
Page 160: ... 158 10 KX SM 148 ...
Page 161: ... 159 10 KX SM 148 9 Duct connected Compact and Flexible type FDUH PJC012D207 a ...
Page 163: ... 161 10 KX SM 148 ...
Page 164: ... 162 10 KX SM 148 PHA012D039 10 Wall mounted type FDK ...
Page 165: ... 163 10 KX SM 148 ...
Page 166: ... 164 10 KX SM 148 ...
Page 170: ... 168 10 KX SM 148 PGF012D004 12 Floor standing 2 way type FDFW ...
Page 171: ... 169 10 KX SM 148 ...
Page 173: ... 171 10 KX SM 148 13 Outdoor air processing unit type FDU F PJD012D059 ...
Page 174: ... 172 10 KX SM 148 ...
Page 175: ... 173 10 KX SM 148 ...
Page 184: ... 10 KX SM 148 182 ...
Page 212: ... 210 10 KX SM 148 2 model type DIS model type HEAD ...
Page 213: ... 211 10 KX SM 148 2 2 ...
Page 214: ... 212 10 KX SM 148 2 2 2 2 2 ...