27
-
'10 • KX-SM-148
(C) Data output
(1) 7-segment and operation data retention
(a) 7-segment display
Operation information is displayed for checking various operation data during test run and for helping malfunction
diagnosis at servicing. Input data to microcomputer, contents of outdoor unit control, indoor unit registration information,
or other, are mainly displayed on the 7-segment LED.
(i) Operation information display
➀
Displays each item at 7-segment of 3-digit × 2 on the outdoor unit PCB.
➁
Display is controlled with the following buttons.
SW9: Setting button for order of 10 of display code
SW8: Setting button for order of 1 of display code
SW7: Data erase/write button
➂
Select the order of 10 for the code No. of each item with SW9 or SW8 for the order of 1.
Following identification alphabets are used at the code display.
“C”: “C00” – “C99”
“P”: “P00” – “Pxx” (up to a place where content is specified)
➃
Code [C96]is operable item. It is possible to delete the retained operation data (data of 30 minutes preceding an
anomalous stop) by following resetting procedure.
<Resetting operation>
• Select code [C96]. If any anomalous data is retained, the data display [dEL] is shown.
• Pressing SW7 for 3 seconds erases the memory data on RAM.
(EEPROM data are not erased.)
• As the data are erased, the data display shows [- - -].
When no anomalous data are retained, it displays [---] as well.
• Unless the reset operation is performed, data are retained. Therefore, if normal operation is resumed without
the reset operation and an anomalous stop occurs again, no new anomalous data cannot be retained, but
former anomalous data are still retained unchanged.
➄
If you press SW8 (order of 1), the number changes 0
2 ... 9
0.
➅
If you press SW9 (order of 10), the number jumps to the leading code of each order of 10.
Data display [Cxx] and setting value display [Pxx] are considered to be continuous.
Example: Pressing SW9 at [C07] it changes to [C10]
: Pressing SW9 at [C90], it changes to [P00]
➆
Codes [C44
or 45
] are operable items. With the following reset operation, the cumulative compressor operation
time corresponding to the code No. can be erased (reset). (Reset of operation time after replacing the compressor)
<Resetting operation>
• Select codes [C44
or 45
]. Cumulative compressor operation time up to present is displayed.
• Pressing SW7 for 3 seconds erases the memory data.
However, the cumulative compressor operation time data in the 30 minutes log data preceding an anomalous
stop (if this retained log data are not deleted) are not erased by this procedure.
➇
Data display for spare items is left in blank.
➈
When it is set to the auto feed display [C99], the data [C00] to [C29] are displayed one after another.
→ <Sensor value, actuator information>
When the data [C00] to [C29] are being displayed one after another, if SW8 or SW9 is pressed, the display changes
to show [C00].
(ii) When the temperature is below -10.0°C for the display of discharge pressure saturated temperature and suction
pressure saturated temperature, the fraction after decimal point is rounded up. (Because the range of 7-segment
display is 3-digit.)
(iii) Return the error No. display after an error to the normal display by turning ON the dipswitch SW3-1.
Summary of Contents for KX6 series
Page 106: ... 104 10 KX SM 148 Models FDC335KXE6M FDCS335KXE6M PCB003Z185 ...
Page 108: ... 106 10 KX SM 148 2 Ceiling cassette 4 way Compact type FDTC Models All moddels A PJA003Z341 ...
Page 111: ... 109 10 KX SM 148 b Duct type Models All models PJC001Z281 ...
Page 112: ... 110 10 KX SM 148 5 Ceiling cassette 1 way type FDTS Model FDTS45KXE6D B PJC001Z195 ...
Page 113: ... 111 10 KX SM 148 Model FDTS71KXE6D B PJC001Z196 ...
Page 116: ... 114 10 KX SM 148 Models FDUM112KXE6D 140KXE6D C PJR002Z259 ...
Page 120: ... 118 10 KX SM 148 Model FDK71KXE6D PHA001Z030 ...
Page 122: ... 120 10 KX SM 148 Models FDE71KXE6D 112KXE6D 140KXE6D C PFA003Z827 ...
Page 123: ... 121 10 KX SM 148 12 Floor standing 2 way type FDFW Models All models A PGF000Z004 ...
Page 127: ... 125 10 KX SM 148 5 APPLICATION DATA 5 1 Installation of indoor unit PJF012D016 a ...
Page 128: ... 126 10 KX SM 148 PJF012D016 A 1 Ceiling cassette 4way type FDT ...
Page 129: ... 127 10 KX SM 148 ...
Page 130: ... 128 10 KX SM 148 ...
Page 141: ... 139 10 KX SM 148 4 Ceiling cassette 1way compact type FDTQ PJC012D121 ...
Page 142: ... 140 10 KX SM 148 ...
Page 143: ... 141 10 KX SM 148 ...
Page 146: ... 144 10 KX SM 148 2 Parts Models QR PNA 14W ER QR PNB 14W ER PJC012D102 h ...
Page 148: ... 146 10 KX SM 148 ...
Page 149: ... 147 10 KX SM 148 5 Ceiling cassette 1way type FDTS PJC012D016 ...
Page 150: ... 148 10 KX SM 148 ...
Page 151: ... 149 10 KX SM 148 ...
Page 152: ... 150 10 KX SM 148 6 Duct connected High static pressure type FDU PJD012D053 ...
Page 153: ... 151 10 KX SM 148 ...
Page 154: ... 152 10 KX SM 148 ...
Page 158: ... 156 10 KX SM 148 8 Duct connected thin Low static pressure type FDUT PJM012D032 B ...
Page 159: ... 157 10 KX SM 148 ...
Page 160: ... 158 10 KX SM 148 ...
Page 161: ... 159 10 KX SM 148 9 Duct connected Compact and Flexible type FDUH PJC012D207 a ...
Page 163: ... 161 10 KX SM 148 ...
Page 164: ... 162 10 KX SM 148 PHA012D039 10 Wall mounted type FDK ...
Page 165: ... 163 10 KX SM 148 ...
Page 166: ... 164 10 KX SM 148 ...
Page 170: ... 168 10 KX SM 148 PGF012D004 12 Floor standing 2 way type FDFW ...
Page 171: ... 169 10 KX SM 148 ...
Page 173: ... 171 10 KX SM 148 13 Outdoor air processing unit type FDU F PJD012D059 ...
Page 174: ... 172 10 KX SM 148 ...
Page 175: ... 173 10 KX SM 148 ...
Page 184: ... 10 KX SM 148 182 ...
Page 212: ... 210 10 KX SM 148 2 model type DIS model type HEAD ...
Page 213: ... 211 10 KX SM 148 2 2 ...
Page 214: ... 212 10 KX SM 148 2 2 2 2 2 ...