Error code
Remote controller:
7-segment display:
LED
Green
Red
Indoor
Outdoor
Content
–
78
–
'10 • KX-SM-148
E36
E36-3
Liqiud flooding anomaly
Keeps flashing
Stays Off
Keeps flashing 3 times flash
1. Applicable model
5. Troubleshooting
Outdoor units
Diagnosis
Countermeasure
Are there
any wrong connection of
refrigerant piping and/or signal wiring ?
. Check the numbers of connected indoor units
recognized by outdoor unit in comparison
with those numbers in
utility drawing
Are there any
excessive refrigerant charged at site?
. Check the calculation result of additional
refrigerant charging amount and the
record of additional refrigerant
charged amount
Are there any
leakage of refrigerant through
valve sheet of SV1?
. Check the temperature difference between
before and after SV1
Are there any
fault in subcooling coil circuit ?
. Check whether the EEVSC is kept open
. Check whether the thermistor of Tho-H is
inserted in the thermistor holder properly
(at cooling mode)
. Check whether the characteristics
of Tho-H and PSL
is OK
Is the
superheat control of
indoor unit OK at cooling mode?
. Check whether the indoor EEV is kept open or not
. Check whether Thi-R1, R2 are installed at proper
position or the characteristics of them are OK
. Check whether the air filter is clogged
. Check whether the indoor
fan rotates
Is the
superheat control of
outdoor unit OK at heating mode?
. Check whether EEVH1 is kept open or not
. Check whether Tho-R1, R2 are installed at proper
position or the characteristics of them is OK
. Check whether the characteristics of PSL are OK
. Check whether the fin of outdoor heat exchanger
is clogged with snow, ice or dust
. Check whether the outdoor
fan rotates
Save data for 30 minutes before stopping in Mente PC
Is the characteristics of Tho-C1 OK ?
NO
NO
NO
NO
NO
NO
NO
YES
YES
YES
YES
YES
YES
YES
Check and save the data of
operating condition
Check the ROM version
Comfirmation of SV1 operation
Correct the connection of
refrigerant piping and/or
signal wiring properly
Adjust refrigerant amount
properly
Replace SV1
Replace the coil of SV1
•
Replace EEVSC
•
Check the coil of EEVSC
Replace the coil of EEVSC
• Replace Tho-H
• Replace PSL
•
Replace indoor EEV
•
Check the coil of EEV
Replace the coil of EEV
•
Check the installed position
of Thi-R1, R2, R3
Replace Thi-R, if necessary
• Check the air filter
•
Check the connection of indoor
fan motor connector
Replace indoor fan motor
*
By checking Thi-R1, R2, R3
from indoor unit operation data
of Mente PC, specify the indoor
unit which tends to be liquid
flooding (Thi-R3
.=.Thi-R2 shows
the probability of liquid flooding)
•
Replace EEVH1
•
Check the coil of EEVH1
Replace the coil of EEVH1
•
Check the installed position of
Tho-R1, R2, R3
Replace Tho-R, if necessary
•
Clean the fin of outdoor heat
exchanger
•
Check the connection of
outdoor fan motor connector
Replace outdoor fan motor
• Replace Tho-C1
Correct the data with Mente PC
and ask our consultation
2. Error detection method
When 5ºC or lower of the
under-dome temperature
superheat is detected for 15
minutes continuously or for 30
minutes continuously.
3.
Condition of error displayed
When above anomaly is
detected 3 times within 90
minutes.
4. Presumable cause
• Unmatching of refrigerant
piping and/or signal wiring
• Overcharging of refrigerant
• Anomalous control of
superheat
• Anomalous circuit of liquid
refrigerant by-pass
• Anomalous refrigerant circuit
of subcool coil
• Under-dome temperature
(Tho-D1) anomaly
Note:If the error does not recur, connect the Mente PC and continue to collect data.
Summary of Contents for KX6 series
Page 106: ... 104 10 KX SM 148 Models FDC335KXE6M FDCS335KXE6M PCB003Z185 ...
Page 108: ... 106 10 KX SM 148 2 Ceiling cassette 4 way Compact type FDTC Models All moddels A PJA003Z341 ...
Page 111: ... 109 10 KX SM 148 b Duct type Models All models PJC001Z281 ...
Page 112: ... 110 10 KX SM 148 5 Ceiling cassette 1 way type FDTS Model FDTS45KXE6D B PJC001Z195 ...
Page 113: ... 111 10 KX SM 148 Model FDTS71KXE6D B PJC001Z196 ...
Page 116: ... 114 10 KX SM 148 Models FDUM112KXE6D 140KXE6D C PJR002Z259 ...
Page 120: ... 118 10 KX SM 148 Model FDK71KXE6D PHA001Z030 ...
Page 122: ... 120 10 KX SM 148 Models FDE71KXE6D 112KXE6D 140KXE6D C PFA003Z827 ...
Page 123: ... 121 10 KX SM 148 12 Floor standing 2 way type FDFW Models All models A PGF000Z004 ...
Page 127: ... 125 10 KX SM 148 5 APPLICATION DATA 5 1 Installation of indoor unit PJF012D016 a ...
Page 128: ... 126 10 KX SM 148 PJF012D016 A 1 Ceiling cassette 4way type FDT ...
Page 129: ... 127 10 KX SM 148 ...
Page 130: ... 128 10 KX SM 148 ...
Page 141: ... 139 10 KX SM 148 4 Ceiling cassette 1way compact type FDTQ PJC012D121 ...
Page 142: ... 140 10 KX SM 148 ...
Page 143: ... 141 10 KX SM 148 ...
Page 146: ... 144 10 KX SM 148 2 Parts Models QR PNA 14W ER QR PNB 14W ER PJC012D102 h ...
Page 148: ... 146 10 KX SM 148 ...
Page 149: ... 147 10 KX SM 148 5 Ceiling cassette 1way type FDTS PJC012D016 ...
Page 150: ... 148 10 KX SM 148 ...
Page 151: ... 149 10 KX SM 148 ...
Page 152: ... 150 10 KX SM 148 6 Duct connected High static pressure type FDU PJD012D053 ...
Page 153: ... 151 10 KX SM 148 ...
Page 154: ... 152 10 KX SM 148 ...
Page 158: ... 156 10 KX SM 148 8 Duct connected thin Low static pressure type FDUT PJM012D032 B ...
Page 159: ... 157 10 KX SM 148 ...
Page 160: ... 158 10 KX SM 148 ...
Page 161: ... 159 10 KX SM 148 9 Duct connected Compact and Flexible type FDUH PJC012D207 a ...
Page 163: ... 161 10 KX SM 148 ...
Page 164: ... 162 10 KX SM 148 PHA012D039 10 Wall mounted type FDK ...
Page 165: ... 163 10 KX SM 148 ...
Page 166: ... 164 10 KX SM 148 ...
Page 170: ... 168 10 KX SM 148 PGF012D004 12 Floor standing 2 way type FDFW ...
Page 171: ... 169 10 KX SM 148 ...
Page 173: ... 171 10 KX SM 148 13 Outdoor air processing unit type FDU F PJD012D059 ...
Page 174: ... 172 10 KX SM 148 ...
Page 175: ... 173 10 KX SM 148 ...
Page 184: ... 10 KX SM 148 182 ...
Page 212: ... 210 10 KX SM 148 2 model type DIS model type HEAD ...
Page 213: ... 211 10 KX SM 148 2 2 ...
Page 214: ... 212 10 KX SM 148 2 2 2 2 2 ...