1
Standard signal receiving range
[Condition]
Illuminance at the receiver area: 360 lux.
(When no lighting fixture is located within 1m of
indoor unit in an ordinary office)
Wireless remote controller unit operation distance
2
Points for attention in connecting a plural
number of indoor units
[Condition]
Illuminance at the receiver area: 360 lux.
(When no lighting fixture is located within 1m of
indoor unit in an ordinary office)
When the remote control unit is used with the
aforementioned interference-prevention setting,
a minimum distance guaranteeing the
prevention of unintended unit responses is 5m.
Please operate remote control unit switches with the unit faced correctly
toward the indoor unit's receiver section.
Effective operation distance can vary with the luminance around the
receiver and the reflection from walls of the room.
When the receiver is exposed to intensive light such as from the direct
sun or a strong light, it may become operable only from a short distance
or unable to receive signals at all.
3
FDEN (continued)
4
Remote controller
A two-digit indicator (7-segment indicator) is provided on the receiver section.
(1) An indication will be displayed for one hour after power on.
(2) An indication appears for 3.5 seconds when a “Stop” command is sent from the wireless remote control
unit while the air conditioner is not running.
(3) An indication appearing in (1) or (2) above will go off as soon as the unit starts operation.
(4) When there are no error records to indicate, addresses are displayed for all of the connected units.
(5) When there are some error records remaining, the error records are displayed.
(6) Error records can be cleared by transmitting a “Stop” command from the wireless remote control unit, while
the backup switch is depressed.
How to read the two-digit display
A backup switch is provided on the receiver section of the panel surface.
When operation from the wireless remote control unit is not possible (due to flat batteries, a mislaid unit, a unit
failure), you can use it as an emergency means. You should operate this switch manually.
(1) If pressed while the air conditioner is in a halt, it will cause the air conditioner to start operation in the
automatic mode.
Wind speed: Hi fan, Temperature setting: 23°C, Louver: horizontal
(2) If pressed while the air conditioner is in operation, it will stop the air conditioner.
Backup button
• After safety confirmation, turn on the power.
• Transmit a cooling operation command with the wireless remote control unit, while the backup switch on the
receiver is depressed.
• If the backup switch on the receiver is pressed during a test run, it will end the test run.
If you cannot operate the unit properly during a test run, please check wiring by consulting with inspection
guides.
Cooling test run operation
Pressing ACL and AIR FLOW button at the same time or inserting the batteries with pressing AIR FLOW
button will customize the signal.
ATTENTION
When the batteries are removed, the setting will return to the default setting.
Please make sure to reset it when the batteries are replaced.
Caution
Instruct the customer to set the mentioned above when replacing the batteries.
(How to set is also mentioned in the user’s manual attached on the air conditioner.)
Setting to avoid mixed communication
3
FDEN (continued)
3
(Top view)
60°
5m
5m
Receivable range
60°
5m
Receivable range
Wireless remote
control unit
Ceiling surface
Floor surface
Within 5m
1m
2.4m
Backup switch
7-segment indicator
Light receiving section
TIMER
CHECK RUN
VRF system (except heat recovery 3-pipe system)
cannot be operated in Auto mode.
Make sure to set the remote controller for the models
so as not to be able to choose Auto mode.
Pushing ACL and MODE button at the same time or
inserting the batteries with pressing MODE button
will make auto mode operation.
Setting to disable the Auto mode operation
Auto mode operation setting
Radio prevention mode
60°
5m
Receivable range
(Top view)
PFA012D620
4