'11•SAF-T-161
(5) Return air temp. control
・
Samecontrolasnormalairconditioner,RAC,PAC,KX...
・
ThermoON/OFFcontrol:
Temp.differencebetweenR/Atemp.sensor(orR/Csensor)
andsettemp.byR/C.
(6) Supply air temp. control
・
TargetS/Atemp.isfixedandcanbeadjustedbyRC-E3/4.
・
ThermoON/OFFcontrol:
Temp.differencebetweenR/Atemp.sensor(orR/Csensor)
andsettempbyR/C(sameasreturnairtemp.control)
・
Cooling:Setreturnairtemp.mustbegreaterthanTargetsupplytemp.
Heating:Setreturnairtemp.mustbelessthanTargetsupplytemp.
(Ifnot,Settemp.becomesTargetsupplytemp.)
Return air temp.
≒
Set R/A temp.
Supply air temp.
≒
Target S/A temp.
Return air temp. control
R/A temp. is set by R/C
Return air temp.
becomes Set R/A temp.