'11•SAF-T-161

Ԟ

Drain pipe

Work procedure 

1.  Remove the flare nut and blind flanges on the pipe of the indoor unit.

 

̪

Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving torque 

to the nut with another spanner in order to avoid unexpected stress to the copper pipe, and then 
remove them.

(Gas may come out at this time, but it is not abnormal.)

 

٨

Pay attention whether the flare nut pops out. (as the indoor unit is sometimes pressured.)

2.  Make a flare on liquid pipe and gas pipe, and connect the refrigeration pipes on the indoor unit.
 

̪

Bend the pipe with as big radius as possible and do not bend the pipe repeatedly. In addition, 

do not twist and crush the pipes.

 

̪

Do a flare connection as follows:

 

٨

Make sure to loosen the flare nut with holding the nut on pipe side with a spanner and giving 

torque to the nut with another spanner in order to avoid unexpected stress to the copper 
pipe, and then remove them.

 

٨

When fastening the flare nut, align the refrigeration pipe with the center of flare nut, screw 

the nut for 3-4 times by hand and then tighten it by spanner with the specified torque 
mentioned in the table below. Make sure to hold the pipe on the indoor unit securely by a 
spanner when tightening the nut in order to avoid unexpected stress on the copper pipe.

3.  Cover the flare connection part of the indoor unit with attached insulation material after a gas 

leakage inspection, and tighten both ends with attached straps.

 

٨

Make sure to insulate both gas pipes and liquid pipes completely.

   

̪

Incomplete insulation may cause dew condensation or water dropping. 

4.  Refrigerant is charged in the outdoor unit.
  As for the additional refrigerant charge for the indoor unit and piping, refer to the installation 

manual attached to the outdoor unit.

Caution

٨

Install the drain pipe according to the installation manual in order to drain properly.

  Imperfection in draining may cause flood indoors and wetting the household goods, etc.

٨

Do not put the drain pipe directly into the ditch where toxic gas such as sulfur, the other harmful and

  inflammable gas is generated. Toxic gas would flow into the room and it would cause serious 

damage to user’s health and safety (some poisoning or deficiency of oxygen). In addition, it may 
cause corrosion of heat exchanger and bad smell.

٨

Connect the pipe securely to avoid water leakage from the joint.

٨

Insulate the pipe properly to avoid condensation drop.

٨

Check if the water can flow out properly from both the drain outlet on the indoor unit and the end 
of the drain pipe after installation.

٨

Make sure to make descending slope of greater than 1/100 and do not make up-down bend and/or trap 
in the midway. In addition, do not put air vent on the drain pipe. Check if water is drained out properly from 
the pipe during commissioning. Also, keep sufficient space for inspection and maintenance.

Work procedure

1.  Make sure to insert the drain hose (the end mode of soft PVC) to the end of the step part of 

drain socket.

  Attach the hose clamp to the drain hose around 10mm from the end, and fasten the screw 

within 5mm left to the nut.

ޓ٨

Do not apply adhesives on this end.

ޓ٨

Do not use acetone-based adhesives to connect to the drain socket.

Type

SAF-DX1000E6

SAF-DX800E6

SAF-DX500E6

SAF-DX350E6

SAF-DX250E6

φ

 9.52

φ

 15.88

φ

 6.35

φ

 12.7

φ

 6.35

φ

 12.7

φ

 6.35

φ

9.52

φ

 6.35

φ

9.52

Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe
Liquid pipe
Gas pipe

Flare connection
Flare connection
Flare connection
Flare connection
Flare connection
Flare connection
Flare connection
Flare connection
Flare connection
Flare connection

Strap (Accessory)

Pipe cover (Accessory)

The thickness of insulation should be 20mm or more.

Ԝ

Duct Work

Ԙ

No air filter is attached to the main unit of air conditioner. Assemble an air filter in the suction 
grill for convenience of cleaning.

ԙ

Select appropriate location and form for the air outlet to distribute air throughout the room. 
Moreover, the air outlet should be able to adjust the air flow volume.

Ԛ

An access hole must be provided at the ceiling. It is indispensable to maintain electrical 
equipment, motor and functional items, and to wash the heat exchanger.

ԛ

Duct must be heat-insulated to prevent dewing. Necessary thickness of insulator is 65 mm 
(JIS A9501).

Humidifier

Air outlet

Direct expansion 

coil kit

Total heat exchanger 

with humidifier

Access hole

(450

)

Refrigerant pipe

250mm

(Section where attached 

 in a straight line)

Drain socket

Drain hose

Stage difflernce part

2.  Prepare a joint for connecting VP-20 pipe, adhere and connect the joint to the drain hose 

(the end made of rigid PVC), and adhere and connect VP-20 pipe (prepare on site).

 

̪

As for drain pipe, apply VP-20 made of rigid PVC which is on the market.

 

٨

When installing drain pipe, use VP-20 for the pipe goes up the closest to the unit, and 
VP-25 or higher number product for farther pipes.

 

٨

Make sure that the adhesive will not get into the supplied drain hose.

    It may cause the flexible part broken after the adhesive is dried up and gets rigid.
 

٨

The flexible drain hose is intended to absorb a small difference at installation of the unit 
or  drain pipes. Intentional bending, expanding may cause the flexible hose broken and 
water leakage.

3.  Make sure to make descending slope of greater than 1/100 and do not make up-down bend 

and/or trap in the midway.

 

٨

Pay attention not to give stress on the pipe on the indoor unit side, and support and fix the 
pipe as close place to the unit as possible when connecting the drain pipe.

 

٨

Do not set up air vent.

٨

When sharing a drain pipe for more than 
one  unit,  lay  the  main  pipe  100mm 
below  the  drain  outlet  of  the  unit.  In 
addition, select VP-30 or bigger size for 
main drain pipe.

Descending slope greater than 1/100

As wide as possible 

(about100mm)

Insulation material  

Supporting metal

Descending slope greater than 1/100

Air vent

No bump

No trap  

Not touching the water

Trapped air will 

generate noises.

VP-30 or bigger

1.5m~2m

Pipe cover (small)

(For insulation) (Accessory)

Pipe cover (For insulation)

(Prepare on site)

Unit 

Pipe cover (big)

(For insulation) (Accessory)

VP-20

(Prepare on site)

Joint for VP-20

(Prepare on site)

VP-25

(Prepare on site)

Drain hose

(Accessory)

Drain socket

 Clamp (Accessory)
(No adhesive allowed)

Caution

٨

Use the new refrigerant pipe.

ޓ

When re-using the existing pipe system for R22 or R407C, pay attention to the following items.

ޓ࡮

Change the flare nuts with the attached ones (JIS category 2), and reprocess the flare parts.

ޓ࡮

Do not use thin-walled pipes.

٨

Use phosphorus deoxidized copper alloy seamless pipe (C1220T specified in JIS H3300) for refrigeration pipe installation.

ޓ

In addition, make sure there is no damage both inside and outside of the pipe, and no harmful 

substances such as sulfur, oxide, dust or a contaminant stuck on the pipes.

 

٨

Do not use any refrigerant other than R410A.

ޓ

Using other refrigerant except R410A (R22 etc.) may degrade inside refrigeration oil. And air getting into 

refrigeration circuit may cause over-pressure and resultant it may result in bursting, etc.

٨

Store the copper pipes indoors and seal the both end of them until they are brazed in order to avoid any dust, dirt or 

water getting into pipe. Otherwise it will cause degradation of refrigeration oil and compressor breakdown, etc.

٨

Use special tools for R410 refrigerant.

Piping work

When conducting piping work, make sure to allow the pipes 
to be aligned in a straight line for at least 250 mm, as shown 
in the left illustration. (This is necessary for the drain pump 
to function)

 Drain socket

Metal plate

10mm

Hose clamp

Fasten the screw within 5 mm left to the nut.

Drain hose

OA

EA

RA

SA

Ceiling 

surface

ԝ

Refrigerant pipe

Suction inlet
(with air filter)

4.  Insulate the drain pipe.
 

٨

Be sure to insulate the drain socket and rigid PVC pipe installed indoors otherwise it may 

cause dew condensation and water leakage.

 

 

̪

After drainage test implementation, cover the drain socket part with pipe cover (small size), then 

use the pipe cover (big size) to cover the pipe cover (small size), clamps and part of the drain 
hose, and fix and wrap it with tapes to wrap and make joint part gapless.

Summary of Contents for SAF-DX1000E6

Page 1: ...X1000E6 Fresh Air DX Assembly Models 1 Regarding the Outdoor unit series refer to the following table Note Reference manuals No Data book 09 KXR SM 130 Models 4㨪6HP 8㨪12HP 14㨪48HP Heat recovery 3 pipe ststems Technical manual Service manual 08 KX T 117 09 KX DB 124 09 KX SM 125 09 KX DB 127 09 KX SM 128 09 KXR DB 129 Manual No 11 SAF T 161 updated March 31 2011 ...

Page 2: ...tions 3 3 Exterior dimensions 4 4 Electrical wiring 13 5 Internal resistance characteristics 14 6 Range of usage limitations 15 7 Operation control function by the indoor controller 16 8 User s manual 22 9 Installation manual 23 10 Application example 32 ...

Page 3: ...as shown in following table Select SAF DX according to the processing air volume Mixed use of SAF DX with KX R E6 indoor unit is available Total connectable capacity of KX R E6 indoor units including SAF DX must be within 100 of outdoor unit capacity Connectable outdoor unit are all KX R E6 series 5 to 48HP All two wire remote controller are available and all center console also can be used Model ...

Page 4: ... control of total heat exchanger must be interlocked with SAF DX Both return air temp control and supply air temp control are applicable Switching the control method can be done with the Dip SW on the control PCB FAN OA EA SA RA SAF DX exchanger Total heat SAF DX Total heat exchanger SA RA EA OA supply fresh air Return fresh air temp sensor temp sensor interlock SW7 3 ON OFF Switching between retu...

Page 5: ...WDQGDUG QWHUQDO 5HVLVWDQFH 2XWVLGH DLU LQWDNH LU ILOWHU 4 W 6KRFN YLEUDWLRQ DEVRUEHU QVXODWLRQ QRLVH KHDW 2SHUDWLRQ FRQWURO 2SHUDWLRQ VZLWFK 5RRP WHPSHUDWXUH FRQWURO 6DIHW HTXLSPHQW QVWDOODWLRQ GDWD 5HIULJHUDQW SLSLQJ VL H RQQHFWLQJ PHWKRG 5HIULJHUDQW UDLQ XS NLW UDLQ KRVH QVXODWLRQ IRU SLSLQJ FFHVVRULHV SAF DX250E6 N 9ᨺ G PP NJ RXYHU ILQ LQQHU JURRYHG WXELQJ OHFWURQLF SDQVLRQ 9DOYH 0 3D 3RO XUHWK...

Page 6: ...E VP20 Contents Gas piping Symbol A φ9 52 3 8 Flare Outdoor air duct Air supply duct Inspection hole F G M10 C Label model name Hole for power source line Wiring hole for total enthalpy Hole for communication line Suspension bolts heat exchanger Liquid piping Drain piping Suspension bolts pitch Control box Suspension bolts pitch 373 337 18 18 362 70 70 PCH000Z367 3 Exterior dimensions 1 Without Dr...

Page 7: ...d service φ6 35 1 4 Flare B D E VP20 Contents Gas piping Symbol A φ12 7 1 2 Flare Outdoor air duct Air supply duct Inspection hole F G M10 C Label model name Hole for power source line Wiring hole for total enthalpy Hole for communication line Suspension bolts heat exchanger Liquid piping Drain piping Suspension bolts pitch Control box Suspension bolts pitch 373 337 18 18 362 70 70 Model SAF DX500...

Page 8: ...service φ6 35 1 4 Flare B D E VP20 Contents Gas piping Symbol A φ12 7 1 2 Flare Outdoor air duct Air supply duct Inspection hole F G M10 C Label model name Hole for power source line Wiring hole for total enthalpy Hole for communication line Suspension bolts heat exchanger Liquid piping Drain piping Suspension bolts pitch Control box Suspension bolts pitch 373 337 18 18 362 70 70 Model SAF DX800E6...

Page 9: ... duct Air supply duct A B G 710 250 270 190 160 C D 385 325 710 160 180 220 337 220 27 67 285 315 64 φ 2 5 0 2 φ 2 0 0 Inspection hole 450 100 200 822 450 F G M10 E F C 264 Label model name Hole for power source line Wiring hole for total enthalpy Hole for communication line Suspension bolts heat exchanger Liquid piping Drain piping Suspension bolts pitch Suspension bolts pitch 373 337 18 18 362 7...

Page 10: ...ts Gas piping Symbol A φ9 52 3 8 Flare Outdoor air duct Air supply duct Inspection hole F G M10 Hole for power source line Wiring hole for total enthalpy Hole for communication line Suspension bolts heat exchanger Liquid piping Drain piping Suspension bolts pitch Control box VP25 Notes 1 Drain piping C2 C1 Drain hose Option Local installation C2 Notes 1 Please local arrange connected socket for VP...

Page 11: ... A φ12 7 1 2 Flare Outdoor air duct Air supply duct Inspection hole F G M10 Hole for power source line Wiring hole for total enthalpy Hole for communication line Suspension bolts heat exchanger Liquid piping Drain piping Suspension bolts pitch Control box VP25 Notes 1 Drain piping C2 C1 1 Please local arrange connected socket for VP25 Drain hose Option Local installation C2 Notes C1 600 or less 29...

Page 12: ...Outdoor air duct Air supply duct Inspection hole F G M10 Hole for power source line Wiring hole for total enthalpy Hole for communication line Suspension bolts heat exchanger Liquid piping Drain piping Suspension bolts pitch Control box VP25 Notes 1 Drain piping C2 C1 Drain hose Option Local installation Notes 1 Please local arrange connected socket for VP25 C1 C2 600 or less 295 325 57 Label mode...

Page 13: ... 0 2 φ 2 0 0 Inspection hole 450 100 200 822 450 F G M10 E F 264 Label model name Hole for power source line Wiring hole for total enthalpy Hole for communication line Suspension bolts heat exchanger Liquid piping Drain piping Suspension bolts pitch Notes 1 Please local arrange connected socket for VP25 Drain hose Option Local installation C2 VP25 Notes 1 Drain piping C2 C1 C1 600 or less 295 325 ...

Page 14: ... 12 11 SAF T 161 PJZ000Z274 3 Remote controller Option parts Wired remote controller Model RC E4 ...

Page 15: ...hermistor Remote controller Thermistor Return air Thermistor Service air Thermistor Heat exchanger Relay for DM TB3 Terminal block Signal line mark SW7 2 Reserved SW7 3 SW7 4 Pressure setting XR1 XR2 XR3 XR4 XR5 Option 1 2 3 4 5 6 12 CNT X3 CNW0 RD X6 1 7 5 3 X1 X2 Control PCB DM CNR2 9 WH 3 1 Y BL Y X4 CNR CNI BL SW6 SW5 1 3 1 CNB SW2 SW1 SW4 SW3 SM 1 CNA 5 3 2 4 SW7 F 0 16A LED 3 LED 2 TB3 Y X Y...

Page 16: ...F T 161 SAF DX250E6 350E6 SAF DX500E6 SAF DX800E6 SAF DX1000E6 Air flow m3 h Internal resistance Pa 200 400 600 800 1000 1200 250 300 350 500 10 20 30 40 50 60 70 80 90 100 5 Internal resistance characteristics ...

Page 17: ... 15 11 SAF T 161 6 Range of usage and limitations SAF DX of the front cover 3 3 3 Refer to the front cover Refer to the front cover PCH000Z374 3 3 3 SAF DX of the front cover DX is DX is ...

Page 18: ...ils CND 7 Operation control function by the indoor controller 1 SAF DX Control Section 2 SAF DX Control PCB Signal line Remote controller line Return air temp sensor Supply air temp sensor Heat exchanger temp sensor RRT coil Float switch SAF DX control PCB Terminal block Control box for power cable 1 Total heat exchanger operation command Power line Single phase 220 240V 50Hz 1 The capacity of ind...

Page 19: ...2 should be kept OFF SAF DX Total heat exchanger SA RA EA OA return fresh air temp sensor supply fresh air temp sensor 3 SW7 Function setting 4 Switching return supply air temp control Supply air temp control is available as OA processing unit supply air temp sensor is already equipped When SW7 3 is Off it become return air temp control and indoor EEV is controlled to keep the superheat of heat ex...

Page 20: ... by RC E3 4 Thermo ON OFF control Temp difference between R A temp sensor or R C sensor and set temp by R C same as return air temp control Cooling Set return air temp must be greater than Target supply temp Heating Set return air temp must be less than Target supply temp If not Set temp becomes Target supply temp Return air temp Set R A temp Supply air temp Target S A temp Return air temp control...

Page 21: ... 1 0㷄 Offset 1 0㷄 Offset 1 5㷄 Offset 2 0㷄 Offset 4 0㷄 Offset 3 0㷄 Offset 2 0㷄 Offset 2 0㷄 Offset 3 0㷄 Offset 4 0㷄 Actual meaning Indoor unit function 㪩㪼㫋㫌㫉㫅㩷㪘㫀㫉㩷㪫㪼㫄㫇㪅 09 㪫㪸㫉㪾㪼㫋㩷㫊㫌㫇㫇㫃㫐㩷㪸㫀㫉 㫋㪼㫄㫇㪅㩷㫆㪽㪽㫊㪼㫋㩷 Target supply air temp in heating 36㷄 Target high pressure HP㻍2 75MPa Target supply air temp can be set from 32㷄 to 40㷄 㷄 at 1㷄 step 䃨 Factory default Target supply air temp in cooling 15㷄 Target lo...

Page 22: ...se Remote controller sensor or Remote sensor supply air temp At the intersection of the solid line mark since the room temp gets closer to the set temp the target low pressure is adjusted to increase so that the inverter Hz is decreased and then indoor heat exch temp and supply air temp are increased Example of automatic supply air temp adjust control in cooling Inverter actual Hz Low pressure Ind...

Page 23: ...ault 䋨㷄䋩 䋨㷄䋩 䋨㷄䋩 10 Free cooling function Free cooling is the function to control the opening of the by pass damper of total heat exchanger in cooling By pass damper of the total heat exchanger can be controlled by CnD CND on PCB outputs ON OFF signal according to outdoor temp return temp When using this function the return air temp sensor should be relocated to the position where the outdoor air ...

Page 24: ... setting temperature of the remote controller indicates the outdoor temperature while operating thermostat ON OFF OPERATION MODE select button Dehumidifying operation is prohibited for SAF DX Every time this button is pressed N displays switch as below For the outdoor unit with Duct connected High static pressure outdoor air processing unit FDU F and Fresh Air DX Assembly SAF DX operation in dehum...

Page 25: ...re electrical wiring work It could cause electric shock unit failure and improper running ٨ Perform earth wiring surely Do not connect the earth wiring to the gas pipe water pipe lightning rod and telephone earth wiring Improper earth could cause unit failure and electric shock due to a short circuit ٨ Earth leakage breaker must be installed If the earth leakage breaker is not installed it can cau...

Page 26: ...with the water surface as illustrated below ٤If the unit is not leveled it may cause malfunctions or inoperation of the float switch M10 nut Suspension bolt Spring washer for M10 Unit Washer for M10 Pipe side Pour water Water surface 0 5mm Vinyl hose Let the pipe side be slightly sloped If the measurements between the unit and the ceiling hole do not match upon installation it may be adjusted with...

Page 27: ...reover the air outlet should be able to adjust the air flow volume ԚAn access hole must be provided at the ceiling It is indispensable to maintain electrical equipment motor and functional items and to wash the heat exchanger ԛDuct must be heat insulated to prevent dewing Necessary thickness of insulator is 65 mm JIS A9501 Humidifier Air outlet Direct expansion coil kit Total heat exchanger with h...

Page 28: ...erly done Water leakage Does the air flow falls within the range of It cannot cool or warm Water is drained properly Water leakage Supply voltage is same as mentioned in the model name plate PCB burnt out not working at all There is mis wiring or mis connection of piping PCB burnt out not working at all Earth wiring is connected properly Electric shock Cable size comply with specified size PCB bur...

Page 29: ...fitting may cause abnormal heat and fire ٨Use the genuine optional parts And installation should be performed by a specialist If you install the unit by yourself it could cause water leakage electric shock and fire ٨Do not repair by yourself And consult with the dealer about repair Improper repair may cause water leakage electric shock or fire ٨Consult the dealer or a specialist about removal of t...

Page 30: ...f trial cooling operation Remote controller line No polarity Remote controller line No polarity Operate the remote control unit as follows 1 Starting a cooling test run ԘStart the system by pressing the button ԙSelect Cool with the MODE button ԚPress the TEST button for 3 seconds or longer The screen display will switch to ԛWhen the SET button is pressed while is indicated a cooling test run will ...

Page 31: ...n is by degree F The filter sign is indicated after running for 180 hours The filter sign is indicated after running for 600 hours The filter sign is indicated after running for 1000 hours The filter sign is indicated after running for 1000 hours then it will be stopped by compulsion after 24 hours Make permission prohibition control of function be in effect With the VRF series it is used to stop ...

Page 32: ... function is set 17 Selection is made by the external adjuster control Ԟ Control mode switching ٨The control content of indoor units can be switched in following way is the default setting Switch No control content SW1 Indoor unit address tens place SW2 Indoor unit address ones place SW3 Outdoor unit address tens place SW4 Outdoor unit address ones place SW5㧙1 OFF Use always at OFF Old and new Sup...

Page 33: ...ppen and the data can be confirmed by remote controller Operating procedure 1 Press the button The display change 2 Once press the button and the display change 3 Press the SET button and abnormal operation data mode is started 4 When only one indoor unit is connected to remote controller following is displayed ԘThe case that there is history of abnormal operation Error code and is displayed Examp...

Page 34: ...th multiple SAF DXs Total heat exchanger with big fan capacity SA RA EA OA SAF DX SA SA SAF DX SAF DX RC E4 In case of controlling multiple SAF DXs in combination with a total heat exchanger with big fan capacity interlock all by using one remote controller Remote controller 㹢SA return air Example of the combination with SAF DX and Total heat exchanger Total heat exchanger SA RA EA OA SAF DX Remot...

Page 35: ...tioning Refrigeration Systems 16 5 Konan 2 chome Minato ku Tokyo Japan Fax 03 6716 5926 Because of our policy of continuous improvement we reserve the right to make changes in all specifications without notice Copyright MITSUBISHI HEAVY INDUSTRIES LTD c ...

Reviews: