'11•SAF-T-161
The initial function setting for typical using is performed automatically for a remote control unit and
an indoor unit by the door unit connected, when remote controller and inside unit are connected.
As long as they are used in a typical manner, there wiil be no need to change the initial settings.
If you would like to change the initial setting marked “ ”, set your desired setting as for the
selected item.
The procedure of functional setting is shown as the following diagram.
As for detail of setting, refer to the installation manual of remote controller.
[Flow of function setting]
Start
: While indoor unit do not operate, press “ ” (SET) and “ ” (MODE) button for
3 seconds at the same time.
Finalize : Press “ ” (SET) button.
Reset : Press “ ” (RESET) button.
Select : Press button.
End
: Press button.
It is possible to finish above setting on the way, and unfinished change of setting is unavailable.
“ ” : Initial settings
“ ” : Automatic criterion
As for detail, refer to the installation manual of remote controller.
ԝ
Function Setting by Remote Controller
Only when plural indoor units are connected
Indoor No. selection
01
02
When you use at 50Hz area
When you use at 60Hz area
(Remote controller function)
Temperature setting button is not working
02
03
03
04
04
05
05
06
06
07
07
08
09
08
10
09
11
10
12
11
13
12
13
14
14
15
16
15
17
16
18
19
17
Function
setting
Mode button is not working
This function is not used. Do not change the setting.
This function is not used. Do not change the setting.
This function is not used. Do not change the setting.
This function is not used. Do not change the setting.
This function is not used. Do not change the setting.
Timer button is not working
ON/OFF button
(finished)
Function
setting
If to change re-set with other indoor
unit, push AIRCON NO.
button, and indoor selection indication
(for example: I/U 000) is set back.
Record and save the
setting
(Note3)
(Note2) This is used to change the minimum aperture of expansion
valve during heating.
The functional setting
During air-conditioner stopping push
(SET) + (MODE) button
simultaneously for 3 seconds
(Indoor unit function)
Remote thermistor is not working.
Remote thermistor is working.
Remote thermistor is working, and to be set for pro3.0°C increase in temperature.
Remote thermistor is working, and to be set for pro2.0°C increase in temperature.
Remote thermistor is working, and to be set for pro1.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -1.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -2.0°C increase in temperature.
Remote thermistor is working, and to be set for producing -3.0°C increase in temperature.
In normal working indication, indoor unit temperature is indicated instead of airflow.
(Only the master remote control can be indicated. )
Heating preparation indication should not be indicated.
Temperature indication is by degree C
Temperature indication is by degree F
The filter sign is indicated after running for 180 hours.
The filter sign is indicated after running for 600 hours.
The filter sign is indicated after running for 1000 hours.
The filter sign is indicated after running for 1000 hours,
then it will be stopped by compulsion after 24 hours.
Make permission/prohibition control of function be in effect.
With the VRF series, it is used to stop all indoor units connected with
the same outdoor unit immediately.
When stop signal is inputed from remote on-off terminal "CNT-6",
all indoor units are stopped immediately.
When heating thermostat is off, to be operated with low air flow.
When heating thermostat is off, to be operated with set air flow.
When heating thermostat is off, to be operated intermittently.
When heating thermostat is off, the fan stops.
When the remote thermistor is working, "FAN OFF" is set automatically.
Do not set when the indoor unit's thermistor is working.
Change of indoor heat exchanger temperature to start frost prevention control.
Working only with the single split series.
To control frost prevention, the indoor fan tap is raised.
Drain pump is on during cooling and dry.
Drain pump is on during cooling, dry and heating.
Drain pump is on during cooling, dry, heating and fan.
Drain pump is on during cooling, dry and fan.
After cooling is stopped, the fan does not perform extra operation.
After cooling is stopped, the fan perform extra operation for half an hour.
After cooling is stopped, the fan perform extra operation for an hour.
After cooling is stopped, the fan perform extra operation for six hours.
After heating is stopped or heating thermostat is off, the fan does not perform extra operation.
After heating is stopped or heating thermostat is off,the fan perform extra operation for half an hour.
After heating is stopped or heating thermostat is off,the fan perform extra operation for two hours.
After heating is stopped or heating thermostat is off, the fan perform extra operation for six hours.
During heating is stopped or heating thermostat is off, the fan perform intermittent operation
for five minutes after twenty minutes' off with low airflow.
During heating is stopped or heating thermostat is off, the fan perform intermittent operation
By setting of SW7-4
for five minutes after five minutes' off with low airflow.
On/Off button is not working
If you change the range of set temperature, the indication of set temperature will vary
following the control.If you change the range of set temperature, the indication of set
temperature will not vary following the control, and keep the set temperature.
If you input into the indoor printed circuit board CNT from outside, the indoor device will
be operated independently following the input from outside.
If you input into indoor printed circuit board CNT from outside, All units which share the
same one remote control network work following the input from outside.
Consult the technical data etc. for each control details
(Note1)
(Note2)
(Note2)
(Note3)
External device control
Pressure control – Standard
Pressure control – Selectable
This function is not used. Do not change the setting.