-
10
-
4.6 Outline of heating operation
(1)
Operation of major functional components
(2)
Fan speed switching
(a)
Auto fan control
The indoor fan is automatically controlled in accordance with the difference between the room temperature (detected by the
room temperature sensor) and the thermostat setting as shown below.
(3)
Thermostat operation
The compressor and outdoor fan and turned on and off as shown below according to the temperature setting.
(4)
Hot keep
This function controls the indoor unit fan speed as shown below in accordance with the temperature sensed by the indoor heat
exchanger sensor.
(a)
When the compressor and outdoor unit fan are operating
Indoor fan motor
Flaps
Display
52C
Outdoor fan motor
ON
ON or OFF
Lights up
ON
OFF
ON
ON or OFF
Lights up
ON
ON
OFF
Stop position control
Lights up or flashes
OFF after stop mode
OFF
4-way valve
Depending on the stop mode
ON
Depending on the stop mode
When the compressor
command is OFF
When the compressor
command is ON
When the compressor goes
OFF due to an abnormal stop.
Functional
components
Item
Air scroll
Swing flap
Swing stop
Auto fan control
Speed 6
Speed 6
Speed 6
Speed 4
Speed 4
Speed 4
AUTO
HIGH
MED
Speed 2
Speed 2
Speed 2
LOW
Flow control
Fan speed switching
Speed 6
Speed 4
Speed 2
Thermostat setting point
-5
-4
-3
-2
-1
0
OFF
ON
Set temp.
Compressor
outdoor fan
+1
Room temp.
Speed 6
Speed 4
Speed 2
Speed 1
OFF
40
34
30
25
15
Auto fan control,
or the set fan speed
Indoor heat exchanger temp. (˚C)
Все каталоги и инструкции здесь:
http
:
//splitoff.ru/tehn-doc.html