- 38 -
5.6 Standard running data:
SRK20MA-S
SRK25MA-S
SRK35MA-S
SRK50MA-S
High pressure (MPa)
Cooling
-
-
-
-
Heating
2.2~2.9
2.2~2.9
2.0~3.2
2.4~3.6
Low pressure (MPa)
Cooling
1.0~1.2
1.0~1.2
0.9~1.2
0.8~1.2
Heating
-
-
-
-
Temp. difference
between inlet and
outlet air of indoor
unit (
℃
)
Cooling
9~10
9~11
8~14
10~16
Heating
9~15
9~16
10~21
10~22
Operating current (A)
Cooling
1.4~4.1
1.4~6.0
1.3~6.6
2.0~10.8
Heating
1.7~5.6
1.7~6.1
1.7~6.6
2.0~13.8
Notes:
①
The above data complies with the standard:
and is measured at the following ambient temperature:
indoor side: cooling……27
℃
DB, 19
℃
WB; heating……20
℃
DB
outdoor side: cooling……35
℃
DB, 24
℃
WB; heating……7
℃
DB, 6
℃
WB
②
The length of the pipe between the indoor and outdoor units is 5 meters in the test. The
length of the pipe supplied with the appliance may vary.
Summary of Contents for SRC20MA-S
Page 10: ... 7 ...
Page 15: ... 12 3 ELECTRICAL WIRING DIAGRAM 3 1 Circuit diagram 20 25 35MA S ...
Page 16: ... 13 3 2 Circuit diagram 50MA S ...
Page 62: ... 59 12 Check method for outdoor unit 1 Circuit diagram of 20 25 and 35MA S outdoor units ...
Page 63: ... 60 2 Circuit diagram of 50MA S outdoor unit ...
Page 84: ... 81 ...
Page 87: ... 84 ...
Page 90: ... 87 ...
Page 93: ... 90 ...
Page 96: ... 93 ...
Page 99: ... 96 ...
Page 102: ... 99 ...
Page 105: ... 102 ...
Page 107: ... 104 18 RYF141A005 PLATE BAFFLE 1 19 RYF111A003F BASE ASSY 1 ...
Page 111: ... 108 19 RYF111A003F BASE ASSY 1 ...
Page 115: ... 112 19 RYF111A003F BASE ASSY 1 ...
Page 119: ... 116 19 RYF111A002G BASE ASSY 1 ...