- 49 -
(e) List of temperatures measured by room temperature sensor, indoor heat exchanger sensor,
outdoor air temp. sensor, and outdoor heat exchanger liquid pipe sensor
Unit:
℃
* If there is no data recorded (the error code is normal), the information of each sensor is as showed in
the table below:
Name of sensor
Value displayed by the sensor when the error
code is normal
Temperature measured by room
temperature sensor
-19
℃
Temperature measured by indoor heat
exchanger sensor
-64
℃
Temperature measured by outdoor air
temp. sensor
-64
℃
Temperature measured by outdoor
heat exchanger liquid pipe sensor
-64
℃
(Example): Temperature measured by room temperature sensor, indoor heat exchanger sensor, outdoor
air temp. sensor and outdoor heat exchanger liquid pipe sensor: “-9
℃
”
Does the buzzer sound?
(Sound means negative)
RUN lamp
(tens place)
TIMER lamp
(ones place)
Yes
(Sounds for
0.1 sec.)
No
(Not sound)
Summary of Contents for SRC20MA-S
Page 10: ... 7 ...
Page 15: ... 12 3 ELECTRICAL WIRING DIAGRAM 3 1 Circuit diagram 20 25 35MA S ...
Page 16: ... 13 3 2 Circuit diagram 50MA S ...
Page 62: ... 59 12 Check method for outdoor unit 1 Circuit diagram of 20 25 and 35MA S outdoor units ...
Page 63: ... 60 2 Circuit diagram of 50MA S outdoor unit ...
Page 84: ... 81 ...
Page 87: ... 84 ...
Page 90: ... 87 ...
Page 93: ... 90 ...
Page 96: ... 93 ...
Page 99: ... 96 ...
Page 102: ... 99 ...
Page 105: ... 102 ...
Page 107: ... 104 18 RYF141A005 PLATE BAFFLE 1 19 RYF111A003F BASE ASSY 1 ...
Page 111: ... 108 19 RYF111A003F BASE ASSY 1 ...
Page 115: ... 112 19 RYF111A003F BASE ASSY 1 ...
Page 119: ... 116 19 RYF111A002G BASE ASSY 1 ...