- 61 -
(13) Check method for outdoor circuit board (inverter)
Make confirmation after checking that the indoor circuit board is normal.
(I) Use a multimeter to conduct inspection.
a) Unplug the plug.
b) Remove the output cables U, V and W (to the compressor) of the power transistor.
(Note: The inspection of inverter can be conducted only after the capacitor is discharged and
after making sure the residual voltage is below 10V.)
c) Insert the plug and press and hold the back-up switch for over 5 sec. till the appliance
commences operation.
d) Measure the voltages between U and V, V and W, and W and U of the power transistor with the
analogue instrument within the range of AC1000V.
If the voltages between U and V, V and W, and W and U as shown in the following figure can be
detected regularly, it indicates the outdoor circuit board is normal.
Compressor start test-running voltage
Press and hold the switch on the main frame for over 5 sec. [ON]
The indoor RUN lamp flashes 2 times and the TIMER lamp flashes 2 times. (Error code 73-76)
Note (1) After the one-time output one minute after this power transistor outputs voltage, the error of
the indoor unit is detected.
(II) Judgment through defective inverter detector (MRE part number: SA01927)
1) Detector setting procedure
a. Switch off the power supply (turn off the switch).
b. Remove the output (power transistor) U, V and W of the inverter (control) circuit board from
the connection of the compressor.
c. Connect the wires of the detector (U=Red, V=White, W=Black) to the terminal wires of the
power transistor.
2) Judging the operation method
a. Insert the plug and press and hold the back-up switch for over 5 sec. till the appliance
commences operation.
b. Confirm the flashing and ON status of the 6 LEDs. The flashing and ON status, which
repeats for 300 sec., is shown below:
Flash (about 3 sec.) ←→ On (about 5 sec.) The flashing stops for one minute and then
repeats for 300 sec.
c. Judge according to the flashing and ON status of the LEDs.
Flashing and ON status of
LEDs
6 LEDs flash at the same
time.
6 LEDs go off or several
LEDs flash or light up.
Inverter
Normal
Defective
d. Let it operate for a while and the error will be indicated (the indoor RUN lamp flashes 2
times and the TIMER lamp flashes 2 times). The output of the inverter stops.
Note: The terminals of the power transistor that control the circuit board are mounted on the back
of the control casing. Remove the control circuit board before connection.
About AC 170V
About 10 sec.
About 300 sec.
The indoor RUN lamp
flashes 2 times and the
TIMER lamp flashes 2
times.
(Error code 73-76)
Insert them into the terminals
of the power transistor
Summary of Contents for SRC20MA-S
Page 10: ... 7 ...
Page 15: ... 12 3 ELECTRICAL WIRING DIAGRAM 3 1 Circuit diagram 20 25 35MA S ...
Page 16: ... 13 3 2 Circuit diagram 50MA S ...
Page 62: ... 59 12 Check method for outdoor unit 1 Circuit diagram of 20 25 and 35MA S outdoor units ...
Page 63: ... 60 2 Circuit diagram of 50MA S outdoor unit ...
Page 84: ... 81 ...
Page 87: ... 84 ...
Page 90: ... 87 ...
Page 93: ... 90 ...
Page 96: ... 93 ...
Page 99: ... 96 ...
Page 102: ... 99 ...
Page 105: ... 102 ...
Page 107: ... 104 18 RYF141A005 PLATE BAFFLE 1 19 RYF111A003F BASE ASSY 1 ...
Page 111: ... 108 19 RYF111A003F BASE ASSY 1 ...
Page 115: ... 112 19 RYF111A003F BASE ASSY 1 ...
Page 119: ... 116 19 RYF111A002G BASE ASSY 1 ...