- 72 -
(1) Tools
designed specifically for R410A
a) Manifold pressure gauge
● As R410A has the property of high pressure, conventional tools can’t be used.
Table 11 Difference between conventional high/low pressure gauge and pressure gauge for R410A
● In order to prevent charging other types of refrigerant accidently, the shapes of the various ports
of the branch manifold are changed.
Table 12 Difference between conventional branch manifold and branch manifold for R410A
Conventional branch manifold
Branch manifold for R410A
Port size
7/16 UNF
20 screw threads per inch
1/2 UNF
20 screw threads per inch
b) Charge hose
● Due to the property of high pressure of R410A, the pressure impedance of the charge hose must
be improved and the material is changed to HFC impedance type material. Furthermore, in
order to comply with the sizes of the various ports of the branch manifold, the sizes of hose
caps are also changed. In addition, in order to prevent gas pressure reaction, the charge hose
with a valve mounted beside the hose cap may be used.
Table 13 Difference between conventional charge hose and charge hose for R410A
Conventional charge hose
Charge hose for R410A
Pressure
impedance
Normal
pressure
3.4 MPa (34 kgf/cm
2
)
5.1 MPa (51 kgf/cm
2
)
Breakdown
pressure
17.2 MPa (172 kgf/cm
2
)
27.4 MPa (274 kgf/cm
2
)
Engineering material
NBR rubber
HNBR rubber
With nylon coating inside
Size of hose cap
7/16 UNF
20 screw threads per inch
1/2 UNF
20 screw threads per inch
c) Electronic loadcell scale for charging refrigerant
● As a kind of HFC, due to the properties of high pressure and high vapor rate, R410A can’t keep
the liquid state and foam state of pneumatolytic refrigerant in the cylinder when the charging
cylinder is used to charge R410A, and the value is difficult to read. Therefore, it is
recommended to use an electronic loadcell scale for charging refrigerant.
● The electronic loadcell scale can measure the weight of the refrigerant cylinder though the 4
supporting points, therefore it has higher strength. The connection of the charge hose has two
ports, one for R22 (7/16 UNF, 20 screw threads per inch) and one for R410A (1/2 UNF, 20
screw threads per inch), so it can be used to charge general refrigerants.
● There are two types of electronic loadcell scale for charging refrigerant, one for 10kg cylinders
and one for 20kg cylinders.
Electronic loadcell scale for 10kg cylinders precision ±2g
Electronic loadcell scale for 20kg cylinders precision ±5g
● Refrigerant can be charged manually by opening/closing the valve.
d) Torque wrench (for rating diameters of 1/2 and 5/8)
● In order to enhance the pressure impedance, the size of flare nut is changed. Therefore the
side-to-center distance of the torque wrench for R410A varies.
Table 14 Difference between conventional wrench and wrench for R410A
Conventional torque wrench
Torque wrench for R410A
For 1/2
(side-to-center
distance x
torque)
24mm X 55N · m
(550 kgf · cm)
26mm X 55N · m
(550 kgf · cm)
For 5/8
(side-to-center
distance x
torque)
27mm x 65N · m
(650 kgf · cm)
29mm x 65N · m
(650 kgf · cm)
Conventional pressure gauge
Pressure gauge designed specifically for R410A
High pressure gauge
(Red)
Compound pressure
gauge (Blue)
Summary of Contents for SRC20MA-S
Page 10: ... 7 ...
Page 15: ... 12 3 ELECTRICAL WIRING DIAGRAM 3 1 Circuit diagram 20 25 35MA S ...
Page 16: ... 13 3 2 Circuit diagram 50MA S ...
Page 62: ... 59 12 Check method for outdoor unit 1 Circuit diagram of 20 25 and 35MA S outdoor units ...
Page 63: ... 60 2 Circuit diagram of 50MA S outdoor unit ...
Page 84: ... 81 ...
Page 87: ... 84 ...
Page 90: ... 87 ...
Page 93: ... 90 ...
Page 96: ... 93 ...
Page 99: ... 96 ...
Page 102: ... 99 ...
Page 105: ... 102 ...
Page 107: ... 104 18 RYF141A005 PLATE BAFFLE 1 19 RYF111A003F BASE ASSY 1 ...
Page 111: ... 108 19 RYF111A003F BASE ASSY 1 ...
Page 115: ... 112 19 RYF111A003F BASE ASSY 1 ...
Page 119: ... 116 19 RYF111A002G BASE ASSY 1 ...