16
-
Model
SRK20ZFX-S, 25ZFX-S, 35ZFX-S
SRK50ZFX-S
Item
Inverter speed
0rps [Comp. stopped]
10 rps [10sec.]
→
0rps [Comp. stopped]
Indoor fan
Hot keep normal mode
→
1st speed
Outdoor fan
Stop
6th speed [1min.]
→
stop
Flap and louver
Horizontal, center
Model
SRK20ZFX-S
SRK25ZFX-S
SRK35ZFX-S
SRK50ZFX-S
Air flow selection
Inverter command speed
30~94rps
30~102rps
20~120rps
Air flow
Depends on inverter command speed.
Inverter command speed
30~94rps
30~102rps
20~120rps
Air flow
8th speed fixed
Inverter command speed
30~66rps
30~72rps
30~76rps
20~80rps
Air flow
6th speed fixed
Inverter command speed
30~38rps
30~42rps
30~46rps
20~38rps
Air flow
4th speed fixed
(c)
Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the temperature of
the indoor unit heat exchanger (detected with Th2, indoor unit heat exchanger sensor) to prevent blowing of cool wind.
¡
Normal mode (Normal heating operation, operation after HI POWER completion)
Note (1) Refer to the table shown above right for the values A and B.
Indoor heat exchanger temp. (˚C)
¡
Values of A, B
A
B
At 0 rps command
22
25
Other than 0 rps
17
19
command
A
B 20~35: 23
°
C
50: 20
°
C
28 29.5
31.5
34
36
37.5
39
40
1st speed
3rd speed
4th speed
5th speed
6th speed
7th speed
OFF
Indoor fan
4.9 Outline of heating operation
(1)
Operation of major functional components in heating mode
(2)
Air flow selection
(a)
Speed of inverter changes within the range of selected air flow.
(b)
When the defrosting, protection device, etc. is actuated, operation is performed in the corresponding mode.
(c)
Outdoor unit blower operates in accordance with the inverter command speed.
(3)
Details of control at each operation mode (pattern)
(a)
Fuzzy operation
Deviation between the room temperature setting correction temperature and the suction air temperature is calculated in
accordance with the fuzzy rule, and used for control of the air capacity and the inverter speed.
(b)
Heating thermostat operation
¡
Operating conditions
If the speed obtained with the fuzzy calculation drops below -24 rps during the heating fuzzy operation, the operation
changes to the heating thermostat operation.
¡
Detail of operation
Auto
HI
MED
LO
Item
Indoor fan motor
ON
ON
OFF
Flap and louver
ON or OFF
ON or OFF
Stop position control
Display
Lights up
Lights up
Lights up or flashes
52C
ON
ON
OFF after stop mode
Outdoor fan motor
OFF (20, 25, 35 type)
ON
OFF (20, 25, 35 type)
Depending on the stop mode (50 type)
Depending on the stop mode (50 type)
4-way valve
Depending on the stop mode
ON
Depending on the stop mode
Electronic expansion valve
Depending on the EEV control
When the inverter
speed is 0rps
When the inverter speed
is other than 0rps
When the inverter speed is 0rps
due to an anomalous stop
Functional
components
8th speed
(20, 25, 35 only)
9th speed