20
-
D
range
C
range
B
range
A
range
(b)
Heating oriented dehumidifying
After interrupting the compressor operation for 3 minutes (by the 3-minute timer) following the determination of heating
oriented dehumidifying, the unit begins in the heating operation. If the room temperature exceeds the setting temperature by
2ºC or more, the unit checks the room temperature at 5-minute intervals and, depending on the result, determines the range
of heating oriented dehumidifying operation.
Operation range
D
C
B
A
Low
–1
0
+2
High
Room temperature – Setting temperature (deg)
(D) (C) (C) (B)
OFF
5th speed
25 sec.
OFF
0
20, 25, 35 type : 38
50 type : 24
20, 25, 35 type : 50
50 type : 40
50 type :
4th speed
20, 25, 35 type : 30
50 type : 20
5th speed
2nd speed
1st speed
50 type :
4th speed
50 type :
4th speed
50 type :
4th speed
Inverter speed
Indoor fan
Outdoor fan
Determination of cooling
oriented dehumidifying
operation range
Temperature check
5 min.
5 min.
5 min.
5 min.
Operation pattern
O
L
M
Low
–1
0
High
Room temperature – Setting temperature (deg)
Operation range
Heating operation
O
range
L
range
M
range
4th speed
OFF
OFF
4th speed
2nd speed
1st speed
20, 25, 35 type : 38
50 type : 28
20, 25, 35 type : 30
50 type : 20
20, 25, 35 type : 48
50 type : 44
0
50 type :
4th speed
50 type :
4th speed
25 sec.
50 type :
4th speed
5th speed
Inverter speed
Indoor fan
Outdoor fan
Determination of heating
oriented dehumidifying
operation range
Temperature check
5 min.
5 min.
5 min.
Depends on
the operation
condition
Operation pattern
Note (1)
Figures in the parentheses
( ) show the values at
ECONOMY operation.
Note (1)
Figures in the parentheses
( ) show the values at
ECONOMY operation.
(2)
Outline of control
(a)
Cooling oriented dehumidifying
Room temperature is checked at 5-minute intervals after selecting the cooling or heating oriented dehumidifying in order to
determine the operation range.
(O) (L) (L)