25
-
Notes (1) RPSmin: The lower one between the outdoor unit speed and the command speed
Note
(2) Values in ( ) are for Type 50.
¡
Temperature list
A
B
C
RPSmin < 40(88)
48 (48.5)
53 (56)
58 (61)
40(88) <= RPSmin < 50(108)
48 (44)
53 (51.5)
58 (56.5)
50(108) <
= RPSmin
48.5 (39)
56 (46.5)
61 (51.5)
(Example) Fuzzy
Indoor unit heat exchanger temperature (˚C)
Lower limit
speed 20(35)rps
After lapse of 20 Sec. or over
(2)
After lapse of 20 Sec. or over
(2)
After lapse of 20 Sec. or over
(2)
B
C
8 rps
(1)
8 rps
0 rps
A
Notes (1) When the indoor unit heat exchanger temperature is in the range of B~C ºC, the speed is reduced by 8 rps at each 20 seconds. When the temperature is C
ºC or over for 1 minute continuously, the inverter is stopped.
(2) When the indoor unit heat exchanger temperature is in the range of A~B ºC, if the inverter command speed is been maintained and the operation has
continued for more than 20 seconds at the same speed, it returns to the normal heating operation.
(3) Indoor blower retains the fan tap when it enters in the high pressure control. Outdoor blower is operated in accordance with the speed.
Unit : ºC
(15) High pressure control
(a)
Purpose:
Prevents anomalous high pressure operation during heating.
(b)
Detector:
Indoor unit heat exchanger sensor (Th2)
(c)
Detail of operation:
(16) Heating low outdoor temperature protective control
◆
20~35 type
<
I
>
(a)
Operating conditions:
When the outdoor air temperature sensor (Th5) is -10ºC or lower continues for 5 minutes while
the outdoor speed is other than 0 rps.
(b)
Operation content:
When the command speed is less than 36 rps, the command speed is forcibly set at 36 rps.
However, when the thermo becomes OFF, the speed is reduced to 0 rps.
(c)
Reset conditions:
When the outdoor air temperature sensor (Th5) becomes -7ºC or higher.
<
II
>
(a)
Operating conditions:
When the outdoor air temperature sensor (Th5) is 0ºC or lower continuously for 5 minutes while
the outdoor speed is other than 0 rps.
(b)
Operation content:
The outdoor fan motor speed is raised to the next higher speed. (Upper limit 7th speed)
(c)
Reset conditions:
When the outdoor air temperature sensor (Th5) becomes 2ºC or higher.
<
III
>
(a)
Operating conditions:
When the temperature sensed by the outdoor heat exchanger sensor (Th4) becomes –10ºC or
lower continuously for 1 minute.
(b)
Operation content:
When the command speed upper limit is set at 102 rps.
(c)
Reset conditions:
When the temperature sensed by the outdoor heat exchanger sensor (Th4) becomes -7ºC or higher.