Operating conditions:
When the outdoor air temperature sensor (Th5) is 22ºC or lower continues for 30 seconds while
outdoor speed is other than 0rps.
(b)
Detail of operation:
◆
20~35 type
1
The lower limit of inverter command speed is set to 30 rps and even if the speed becomes lower than 30 rps, the speed is
kept to 30 rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
2
The upper limit of control speed is set to 60(40) rps and even if the calculated result becomes higher than that after fuzzy
calculation, the speed is kept to 60(40) rps.
22
25
OFF
0
3
Upper limit 40rps
Lower limit 30rps
ON
ON
Upper limit 60rps
Lower limit 30rps
Outdoor air temp.(
°
C)
(c)
Reset conditions:
When the either of the following condition is satisfied
1
When the outdoor air temperature sensor (Th5) becomes 25ºC or higher.
2
When the inverter command speed is 0rps.
◆
50 type
1
The lower limit of inverter command speed is set to 30(44) rps and even if the speed becomes lower than 30(44) rps, the
speed is kept to 30 rps. However, when the thermo becomes OFF, the speed is reduced to 0 rps.
2
The upper limit of control speed is set to 60(50) rps and even if the calculated result becomes higher than that after fuzzy
calculation, the speed is kept to 60(50) rps.
22
25
OFF
0
3
Upper limit 50rps
Lower limit 44rps
ON
ON
Upper limit 60rps
Lower limit 30rps
Outdoor air temp.(
°
C)