56
-
Measure in this section
Operation SW ON
8~10 sec.
0
Output voltage
(ACV)
(Example)
Self-diagnosis display
: Flashes 2 times
◆
Power transistor inspection procedure
1
For about 50 seconds. After being switched on,
the will be a delay of approximately one minute
depending on the conditions.
[Use a tester with a needle indicator for the inspection. (Do not use a digital tester. Check in the AC 300 volt range.)]
(1)
If there is a self-diagnosis display, inspect the compressor system (burns, wiring mistakes, etc.) If no problems are found,
check the output of the power transistor.
(2)
Output inspection procedure
Disconnect the terminals for the compresseor.
If an output such as the one shown in the figure on the below can be measured, the power transistor and the circuit board for
the outdoor unit are normal.
(ii)
DC Fan motor resistance check
Notes (1) Remove the fan motor and measure it without power connected to it.
Notes
(2) If the measured value is left the value when the motor is normal, it means that the fan
motor is faulty.
Measuring Point
Resistance when Normal
6
–
4
(Red – Black)
25 M
Ω
or higher
3
–
4
(White – Black)
30 k
Ω
or higher
FM
0
Outdoor unit
circuit board
DC several V (4 ~ 7 V)
CNA
DC15V
DC308 ~ 336V
GND
(–)
Blue
Y
ellow
White
Black
Red
1
2
3
4
5
6
1
2
3
4
5
6
◆
Outdoor unit fan motor check procedure
This is a diagnostic procedure for determining if the outdoor unit’s fan motor or the circuit board is broken down.
Perform this check after checking if the indoor unit is normal.
(i)
Outdoor unit printed circuit board output check
1) Turn off the power.
2) Disconnect connector CNA for the fan motor in the outdoor unit.
3) Turn on the power, then press the unit ON/OFF button continuously for 5 seconds or longer (to turn the unit ON). When an
indoor unit operates, if there is an output from pin No. (2) in the following diagram for 30 seconds 20 seconds after the unit
ON/OFF button is turned “ON,” the circuit board is normal and the fan motor is faulty. If no voltage is output, the outdoor
unit’s circuit board is faulty and the fan motor is normal.
Note (1) After 3 minutes, the voltage at Pin No. (2) is output again one time for 30 seconds, then the indoor unit detects an error.