4.7 Outline of heating operation
(1)
Operation of major functional components in heating mode
(2)
Details of control at each operation mode (pattern)
(a)
Fuzzy operation
Deviation between the room temperature setting correction temperature and the suction air temperature is calculated in
accordance with the fuzzy rule, and used for control of the air capacity and the inverter speed.
When the defrosting, protection device, etc. is actuated, operation is performed in the corresponding mode.
(b)
Hot keep operation
If the hot keep operation is selected during the heating operation, the indoor blower is controlled based on the temperature of
the indoor unit heat exchanger (detected with Th2, indoor unit heat exchanger sensor) to prevent blowing of cool wind.
Thermostat ON
Thermostat OFF
Defrost
Failure
Heating
Compressor
Indoor fan motor
Outdoor fan motor
4-way valve
30~94rps
30~102rps
20~120rps
30~94ps
30~102rps
20~120rps
30~66rps
30~72rps
30~76rps
20~80rps
30~38rps
30~42rps
30~46rps
20~38rps
SRK20ZGX-S
Model
Fan speed
SRK25ZGX-S
SRK35ZGX-S
SRK50ZGX-S
Auto
MED
HI
LO
(3) Defrosting operation
(a)
Starting conditions (Defrosting operation can be started only when all of the following conditions are met.)
1
After start of heating operation
When it elapsed 35 minutes. (Accumulated compressor operation time)
2
After end of defrosting operation
When it elapsed 35 minutes. (Accumulated compressor operation time)
3
Outdoor unit heat exchanger sensor (Th4) temperature
When the temperature has been below –5ºC for 3 minutes continuously.
4
When the temperature difference between the outdoor air sensor temperature and the outdoor unit heat exchanger sensor
temperature exceeded 20. 25 type: 7.0
°
C, 35 type: 5.0
°
C, 50 type: 4.0
°
C
5
During continuous compressor operation
In addition, when the speed command from the indoor controller of the indoor unit during heating operation has counted
0 rps 10 times or more and all conditions of
1
,
2
,
3
and
5
above and the outdoor air temperature is 3
°
C or less are
satisfied (note that when the temperature for Th4 is -5
°
C or less: 62 rps or more, -4
°
C or less: less than 62 rps), defrost
operation is started.
(b)
Ending conditions (Operation returns to the heating cycle when either one of the following is met.)
1
Outdoor heat exchanger sensor (Th4) temperature: 13ºC or higher
2
Continued operation time of defrosting
→
For more than 10 min.